Installation Guide

Do not use the pump to vent the system. Do not start
the pump before filling the system. Never operate
the pump dry.
The pump should be manually vented as follows to prevent
the possibility of any bearing damage at start-up. The
pump will continue to automatically vent air once manually
vented.
1. Once the system has been filled and vented, open the
isolation valves and slowly remove the indicator plug
in the middle of the nameplate.
2. Allow the air to purge from the pump until water
appears. While air is venting, gently turn shaft and
move it in and out, with a small flat blade screwdriver.
Protect the terminal box from getting wet. After air
has been vented, install and retighten the plug. The
pump can now be started.
GRUNDFOS domestic circulating pumps, installed
properly and sized for correct performance, will operate
quietly and efficiently and provide years of service.
Under no circumstances should the pump be operated
without water circulation or without the minimum required
inlet pressure for prolonged periods of time. This could
result in motor and pump damage.
UPS model pumps are multispeed, and the speed can be
changed by a speed selector switch located on the front
of the terminal box. UP models are single speed.
7.
8.
Limited Warranty
Products manufactured by GRUNDFOS PUMPS
CORPORATION (GRUNDFOS) are warranted to the original user
only to be free of defects in material and workmanship for a period
of 18 months from date of installation, but not more than 24 months
from date of manufacture. GRUNDFOS' liability under this
warranty shall be limited to repairing or replacing at GRUNDFOS'
option, without charge, F.O.B. GRUNDFOS' factory or authorized
service station, any product of GRUNDFOS manufacture.
GRUNDFOS will not be liable for any costs of removal, installation,
transportation, or any other charges which may arise in connection
with a warranty claim. Products which are sold but not
manufactured by GRUNDFOS are subject to the warranty
provided by the manufacturer of said products and not by
GRUNDFOS' warranty. GRUNDFOS will not be liable for damage
or wear to products caused by abnormal operating conditions,
accident, abuse, misuse, unauthorized alteration or repair, or if
the product was not installed in accordance with GRUNDFOS'
printed installation and operation instructions.
To obtain service under this warranty, the defective product must
be returned to the distributor or dealer of GRUNDFOS products
from which it was purchased together with proof of purchase and
installation date, failure date, and supporting installation data.
Unless otherwise provided, the distributor or dealer will contact
the GRUNDFOS factory or authorized service station for
instructions. Any defective product to be returned to the factory
or service station must be sent freight prepaid; documentation
supporting the warranty claim and/or a Return Authorization must
be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES
ARISING FROM INSTALLATION, USE, OR ANY OTHER
CAUSES. THERE ARE NO EXPRESS OR IMPLIED
WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS
FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND
THOSE WARRANTIES DESCRIBED OR REFERRED TO
ABOVE.
Some jurisdictions do not allow the exclusion or limitation of
incidental or consequential damages and some jurisdictions do
not allow limitations on how long implied warranties may last.
Therefore, the above limitations or exclusions may not apply to
you. This warranty gives you specific legal rights and you may
also have other rights which vary from jurisdiction to jurisdiction.
Start-Up
Operation
Failure to Operate
When the pump is first started, the shaft may rotate slowly
until water has fully penetrated the bearings. If the pump
does not run, the shaft can be rotated manually. To
accomplish this, switch off the electrical supply, and close
the isolation valves on each side of the pump. Remove
the indicator plug in the middle of the nameplate. Insert a
small flat blade screwdriver into the end of the shaft, and
gently turn until the shaft moves freely (see Figure 7).
Replace and tighten the plug. Open the isolation valves
and wait 2 to 3 minutes for the system pressure to equalize
before starting the pump.
NOTE: After a long shut down multi-speed pumps should
be started on speed 3 and then adjusted to the regular
setting. The UPS 15-42 has automatic function to assist
in restart.
Wiring diagram for UPS15-42F model multi-speed
pumps.
Installation
Instructions
Maintenance-Free
Circulators
Page 5
Page 6
L-UP-TL-006 Rev. 7/98
PRINTED IN USA
Page 7
Wire the hot lead to terminal "L," neutral wire to terminal "N," and
ground to the grounding terminal. For 230 volt pumps, the two
hot leads should be to "L" and "N" and the ground to the grounding
terminal.