Submittal Sheet
Table Of Contents
- 1. Product description
- 2. Product range
- 3. System applications
- 4. Functions
- Control modes: Quick overview
- Operating modes
- Control modes
- Additional control mode features
- Multipump modes
- Flow estimation accuracy
- Readings on the pump
- Performance overview
- Operating status and pump performance
- Warning and alarm
- Heat energy monitor
- Heat consumption accuracy
- Operating log
- Help and guidance
- Grundfos Eye
- Communication
- Grundfos GO Remote
- Wireless GENIair
- CIM modules
- Available CIM modules
- Grundfos Remote Management
- Digital inputs
- Relay outputs
- Analog input for an external sensor
- External setpoint function
- 5. Operating conditions
- 6. Construction
- 7. Installation
- 8. Operating the product
- 9. Curve conditions
- 10. Performance curves and technical data
- Conversion tables
- MAGNA3 32-60 F (N)
- MAGNA3 32-100 F (N)
- MAGNA3 32-120 F (N)
- MAGNA3 40-80 F (N)
- MAGNA3 40-120 F (N)
- MAGNA3 40-180 F (N)
- MAGNA3 50-80 F (N)
- MAGNA3 50-120 F (N)
- MAGNA3 50-150 F (N)
- MAGNA3 50-180 F (N)
- MAGNA3 65-120 F (N)
- MAGNA3 65-150 F (N)
- MAGNA3 D 65-150 F
- MAGNA3 80-100 F (N)
- MAGNA3 D 80-100 F
- MAGNA3 100-120 F (N)
- MAGNA3 D 100-120 F
- 11. Accessories
- 12. Product numbers
- 13. Grundfos Product Center
Functions
MAGNA3
4
28
Available CIM modules
Module Fieldbus protocol Description Functions
CIM 050
TM06 7238 3416
GENIbus
CIM 050 is a Grundfos communication
interface module used for communication
with a GENIbus network.
CIM 050 has terminals for the GENIbus
connection.
CIM 100
TM06 7279 3416
LonWorks
CIM 100 is a Grundfos communication
interface module used for communication
with a LonWorks network.
CIM 100 has terminals for the LonWorks
connection.
Two LEDs are used to indicate the actual status
of the CIM 100 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate LonWorks communication status.
CIM 200
TM06 7281 3416
Modbus RTU
CIM 200 is a Grundfos communication
interface module used for communication
with a Modbus RTU network.
CIM 200 has terminals for the Modbus
connection.
DIP switches are used to select parity and stop
bits, to select transmission speed and to set line
termination.
Two hexadecimal rotary switches are used to set
the Modbus address.
Two LEDs are used to indicate the actual status
of the CIM 200 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate Modbus communication status.
CIM 260
US 3G/4G
CIM 260 is a Grundfos communication
interface module, which communicates
using Modbus TCP via cellular data
transmission to a SCADA system or SMS
communication to mobile phones.
CIM 260 has a SIM-card slot and an SMA
connection to the cellular antenna.
CIM 260 can be fitted with a lithium-ion battery.
Two LEDs are used to indicate the actual status
of the CIM 260 communication. One LED is used
for indication of correct connection to the pump,
and the other is used to indicate cellular
communication status.
Note: The SIM card is not supplied with CIM 260.
CIM 280
GRM 3G/4G
CIM 280 is a Grundfos communication
interface module which communicates via
cellular network to Grundfos Remote
Management.
CIM 280 has a SIM-card slot and an SMA
connection to the cellular antenna.
CIM 280 can be fitted with a lithium-ion battery.
Two LEDs are used to indicate the actual status
of the CIM 260 communication. One LED is used
for indication of correct connection to the pump,
and the other is used to indicate cellular
communication status.
Note: The SIM card is not supplied with CIM 280.