Submittal Sheet

Table Of Contents
Functions
MAGNA3
4
15
Control modes: Quick overview
AUTO
ADAPT
We recommend this control mode for most heating systems.
During operation, the pump automatically makes the necessary adjustment
to the actual system characteristic.
FLOW
ADAPT
The FLOW
ADAPT
control mode combines a control mode and a function:
The pump is running in AUTO
ADAPT
.
The delivered flow from the pump will never exceed a selected FLOW
LIMIT
.
Proportional pressure
Used in systems with relatively large pressure losses in the distribution
pipes.
The head of the pump will increase proportionally to the flow in the system to
compensate for the large pressure losses in the distribution pipes.
Constant pressure
We recommend this control mode in systems with relatively small pressure
losses.
The pump head is kept constant, independent of the flow in the system.
Constant temperature
In systems with a fixed system characteristic, for example domestic hot-water
systems, the control of the pump according to a constant return-pipe
temperature is relevant.
H
Q
Q
max
90 %
Q
max
25 %
H
auto_min
H
fac
Q
fac
H
Q
H
set
H
set
2
H
Q
H
Q