Submittal Sheet
Table Of Contents
- 1. Product description
- 2. Product range
- 3. System applications
- 4. Functions
- Control modes: Quick overview
- Operating modes
- Control modes
- Additional control mode features
- Multipump modes
- Flow estimation accuracy
- Readings on the pump
- Performance overview
- Operating status and pump performance
- Warning and alarm
- Heat energy monitor
- Heat consumption accuracy
- Operating log
- Help and guidance
- Grundfos Eye
- Communication
- Grundfos GO Remote
- Wireless GENIair
- CIM modules
- Available CIM modules
- Grundfos Remote Management
- Digital inputs
- Relay outputs
- Analog input for an external sensor
- External setpoint function
- 5. Operating conditions
- 6. Construction
- 7. Installation
- 8. Operating the product
- 9. Curve conditions
- 10. Performance curves and technical data
- Conversion tables
- MAGNA3 32-60 F (N)
- MAGNA3 32-100 F (N)
- MAGNA3 32-120 F (N)
- MAGNA3 40-80 F (N)
- MAGNA3 40-120 F (N)
- MAGNA3 40-180 F (N)
- MAGNA3 50-80 F (N)
- MAGNA3 50-120 F (N)
- MAGNA3 50-150 F (N)
- MAGNA3 50-180 F (N)
- MAGNA3 65-120 F (N)
- MAGNA3 65-150 F (N)
- MAGNA3 D 65-150 F
- MAGNA3 80-100 F (N)
- MAGNA3 D 80-100 F
- MAGNA3 100-120 F (N)
- MAGNA3 D 100-120 F
- 11. Accessories
- 12. Product numbers
- 13. Grundfos Product Center
Performance curves and technical data
10
56
MAGNA3Performance curves and technical data
MAGNA3 65-120 F (N) 1 x 115, 230 V, 60 Hz
For product numbers, see page 68.
H
[ft]
0
4
8
12
16
20
24
28
32
36
40
44
Q [US gpm]0 20 40 60 80 100 120 140 160 180 200 220
P1
[W]
0
100
200
300
400
500
600
700
800
H
[ft]
0
4
8
12
16
20
24
28
32
36
40
44
Q [US gpm]
0 20 40 60 80 100 120 140 160 180 200 220
2 V
3 V
4 V
5 V
6 V
7 V
8 V
9 V
10 V
H
[ft]
0
4
8
12
16
20
24
28
32
36
40
44
Q [US gpm]0 20 40 60 80 100 120 140 160 180 200 220
P1
[W]
0
100
200
300
400
500
600
700
800
AUTOADAPT
Proportional pressure Constant pressure 0-10 volts*
Speed
P1 [W]
115 V
I
1
[A]
115 V
P1 [W]
230 V
I
1
[A]
230 V
Min. 20.5 0.36 0.18 20.5
Max. 767 6.75 758 3.32
The pump incorporates overload protection.
Net weights
[lb (kg)]
Ship. vol.
[ft
3
(m
3
)]
47.4 (21.5) 2.12 (0.06)
* External setpoint influence shown with a
setpoint of H
max
Connections: GF53/65 flanges.
See Pipe connections, page 67.
System pressure: Max. 175 psi (1.2 MPa) (12 bar).
Liquid temperature: 14 to 230 °F (-10 to +110 °C) (TF 110).
Also available with: Stainless-steel pump housing, type N.
Specific EEI:
0.17 (115V)
0.17 (230V)
TM05 7652 1413
B2
L5
L1
B7
B4
B6
H3
H1 H6
H4 H2
B1
D1
D2
D3
D4
ØD5
Pump type Dimensions [in (mm)]
MAGNA3 65-120 F (N)
L1 L5 B1 B2 B4 B6 B7 D1 D2
13.4 (340) 8.03 (204) 3.31 (84) 6.46 (164) 2.87 (73) 5.24 (133) 5.24 (133) 2.56 (65) 4.65 (118)
D3 D4 D5 H1 H2 H3 H4 H6
5.0/5.51 (127/140) 7.28 (185) 0.63/0.75 (16/19) 2.91 (74) 12.28 (312) 15.2 (386) 3.7 (94) 2.32 (59)