Submittal Sheet

Table Of Contents
System applications
MAGNA3
3
11
Cooling systems
Fig. 11 Functional drawing of a cooling system in a commercial building
The following sections provide recommendations on
which control mode to choose according to your
application and where the pump is placed in the
system.
In addition, you can use MAGNA3's built-in application
wizard to help you identify which control mode is best
suited your application. See Application wizard, page
42.
4A. Primary/secondary system, primary
pump
Constant temperature
If the setpoint temperature from the chiller is known
and the aim is to maintain this temperature all the way
to the buffer tank, the constant-temperature control
mode can be chosen.
Depending on the position of the pump, the internal or
an external temperature sensor can be used to
measure the temperature.
See Constant temperature, page 20.
Differential temperature
If the design differential temperature across the chiller
is known, the differential temperature control mode can
be selected. This requires an additional temperature
sensor.
See Differential temperature, page 20.
Constant flow
In cases where the chiller is not varying, the pump is
typically started and stopped by the chiller. This
indicates a requirement for constant flow, hence this
being the optimum control mode.
See Constant curve, page 21.
Constant curve
In cases where the chiller is not varying and the
required delta-T is known, the constant-curve control
mode can be used. Here, the constant curve is
adjusted until the desired delta-T is obtained.
See Constant curve, page 21.
TM07 0358 1218
MM
M
T
T
1
2
4
5
78
6
AB
A
3
Pos. Description
1 Cooling tower
2 Cooling source
3 Chiller pump
4 Primary/secondary system
4A Primary pump
4B Secondary pump
5 "Primary only" system
5A Primary pump
6 Air handling unit
7 Fan coil unit
8 Underfloor/ceiling