UP/UPS Pumps Product Guide

Table Of Contents
Technical data
UP Series
6
65
ALPHA2
Approximate power usage
Maximum operating pressures
Maximum operating temperatures
Note: The maximum glycol concentration with clean
water is 0 % glycol at 36 °F (2 °C). A hydraulic
performance change can be expected.
Approvals
TM04 6025 0611
Speed setting
Min.
[W]
Max.
[W]
High, fixed speed III 39 45
Medium, fixed speed II 15 30
Low, fixed speed I 5 8
Constant pressure 8 45
Constant pressure 14 45
Constant pressure 22 45
AUTO
ADAPT
545
Flow range: 0 - 21.5 gpm (0 - 4.9 m
3
/h)
Head range: 0 - 19 ft (0 - 5.8 m)
Motor:
4-pole, synchronous
permanent magnet motor
Max. liquid temperature
(see table below):
230 °F (110 °C)
Min. liquid temperature
(see table below):
36 °F (2 °C)
Max. system pressure: 150 psi (10 bar)
Closed (F, FR) and open systems (SF)
Model Volts Amps Watts Hp Capacitor
ALPHA2 15-55 115 0.65 5-45 0.007 - 0.061 -
Liquid temperature
[°F (°C)]
Minimum inlet pressure
[psi (bar)]
167 (75) 0.75 (0.05)
194 (90) 4.06 (0.28)
230 (110) 15.7 (1.08)
Ambient temperature Liquid temperature
[°F (°C)] Min. [°F (°C)] Max. [°F (°C)]
+32 (0) +36 (+2) +230 (+110)
+50 (+10) +50 (+10) +230 (+110)
+68 (+20) +68 (+20) +230 (+110)
+86 (+30) +86 (+30) +230 (+110)
+95 (+35) +95 (+35) +194 (+90)
+104 (+40) +104 (+40) +158 (+70)
Canadian
EMC Standard:
ICES-003
This Class B digital
apparatus complies with
Canadian
ICES-003
3191277
Conforms to
ANSI/UL Std. 778
Certified to
CAN/CSA Std. C22.2 No. 108
Drinking Water System Component
NSF/ANSI 61
NSF/ANSI 372