Analog input for external sensor
The analog input can be used for the connection of an
external sensor for measuring temperature, pressure,
flow or other parameter.
The analog input can also be used for an external
signal for the control from a BMS system or similar
control system.
The electrical signal for the input can be 0-10 VDC or
4-20 mA.
The selection of electrical signal (0-10 V or 4-20 mA)
can be changed on the control panel or with the
Grundfos GO Remote.
Fig. 40 Analog input for external sensor or control
In order to optimize the pump performance, external
sensors can advantageously be used in the following
cases:
Fig. 41 Wiring, analog input
Fig. 42 Examples of external sensors
For further details, see section Curve conditions, page
32.
Fig. 43 Example of external signal for the control via BMS
or PLC
TM05 3221 1112
Function/control mode Sensor type
Heat energy meter Temperature sensor
Constant temperature Temperature sensor
Proportional pressure Pressure sensor
TM05 3343 1212
signal
sensor
Vcc
24V
I
N
Max.
24 V DC
22 mA
0-10 V DC
4-20 mA
I
IN
24V
Vcc
Signal
Vcc
Signal
TM05 2947 1212
Pos. Sensor type
1
Temperature transmitter, Danfoss type MBT 3560,
1/2" connection and 4-20 mA signal.
2
Pressure transmitter, Grundfos type RPI.
1/2" connection and 4-20 mA signal.