Brochure
Table Of Contents
- 1. Product description
- 2. Type key
- 3. Product range
- 4. Operating conditions
- 5. Construction
- 6. Installation
- 7. Accessories
- 8. Curve conditions
- 9. Performance curves
- 10. Product numbers
- 11. Further product information
Product range
MAGNA3
3
15
Setting values for control modes (Single-head operation)
The setting values for FLOW
ADAPT
and FLOW
LIMIT
are indicated as percent of Q
max
,
The operating range for proportional-pressure and constant-pressure control appears from the individual data sheet.
Constant-curve duty: 0 to 100 % speed.
* Stainless steel version available for single head unit only.
Pump type
AUTO
ADAPT
H
fac
Q
max
FLOW
ADAPT
/ FLOW
LIMIT
Q
fac
Q
min
25 % Q
max
90 %
ft [m]
gpm [m
3
/h]
gpm [m
3
/h] gpm [m
3
/h] gpm [m
3
/h]
MAGNA3 40-80 F (N) 14.8 [4.5] 94.7 [21.5] 57.2 [13] 23.8 [5.4] 85.4 [19.4]
MAGNA3 40-120 F (N) 21.3 [6.5] 112.2 [25.5] 70.4 [16] 28.2 [6.4] 101.2 [23]
MAGNA3 40-180 F (N) 31.2 [9.5] 125.4 [28.5] 66.0 [15] 31.2 [7.1] 113.1 [25.7]
MAGNA3 50-80 F (N) 14.8 [4.5] 129.8 [29.5] 74.8 [17] 32.6 [7.4] 117.0 [26.6]
MAGNA3 50-150 F (N) 26.2 [8.0] 165.0 [37.5] 88.0 [20] 41.4 [9.4] 148.7 [33.8]
MAGNA3 65-120 F (N) 21.3 [6.5] 209.0 [47.5] 132.0 [30] 52.4 [11.9] 188.3 [42.8]
MAGNA3 (D) 65-150 F (N)* 26.2 [8.0] 248.6 [56.5] 176.0 [40] 62.0 [14.1] 224.0 [50.9]
MAGNA3 (D) 80-100 F (N)* 18.0 [5.5] 297.0 [67.5] 206.8 [47] 74.4 [16.9] 267.5 [60.8]
MAGNA3 (D) 100-120 F (N)* 21.3 [6.5] 345.4 [78.5] 250.8 [57] 86.2 [19.6] 311.1 [70.7]