Brochure

Table Of Contents
Product range
MAGNA3
3
21
Available CIM modules
For product numbers, see section CIM modules, page 30.
Module Fieldbus protocol Description Functions
CIM 050
TM05 3812 1612
GENIbus
The CIM 050 is a Grundfos communication
interface module used for communication
with a GENIbus network.
The CIM 050 has terminals for the GENIbus
connection.
CIM 100
TM05 3813 1612
LonWorks
The CIM 100 is a Grundfos communication
interface module used for communication
with a LonWorks network.
The CIM 100 has terminals for the LonWorks
connection.
Two LEDs are used to indicate the actual
status of the CIM 100 communication. One
LED is used for indication of correct
connection to the pump, and the other is used
to indicate LonWorks communication status.
CIM 150
TM05 3814 1612
Profibus DP
The CIM 150 is a Grundfos communication
interface module used for communication
with a Profibus network.
The CIM 150 has terminals for the Profibus
DP connection.
DIP switches are used to set line termination.
Two hexadecimal rotary switches are used to
set the Profibus DP address.
Two LEDs are used to indicate the actual
status of the CIM 150 communication. One
LED is used for indication of correct
connection to the pump, and the other is used
to indicate Profibus communication status.
CIM 200
TM05 3815 1612
Modbus RTU
The CIM 200 is a Grundfos communication
interface module used for communication
with a Modbus RTU network.
The CIM 200 has terminals for the Modbus
connection.
DIP switches are used to select parity and
stop bits, to select transmission speed and to
set line termination.
Two hexadecimal rotary switches are used to
set the Modbus address.
Two LEDs are used to indicate the actual
status of the CIM 200 communication. One
LED is used for indication of correct
connection to the pump, and the other is used
to indicate Modbus communication status.
CIM 300
TM05 3815 1612
BACnet MS/TP
The CIM 300 is a Grundfos communication
interface module used for communication
with a BACnet MS/TP network.
The CIM 300 has terminals for the BACnet
MS/TP connection.
DIP switches are used to set transmission
speed and line termination and to select the
custom Device Object Instance Number.
Two hexadecimal rotary switches are used to
set the BACnet address.
Two LEDs are used to indicate the actual
status of the CIM 300 communication. One
LED is used for indication of correct
connection to the pump, and the other is used
to indicate BACnet communication status.