Install Instructions

Table Of Contents
English (US)
24
The signal relay is operated as follows:
Not active
The signal relay is deactivated.
Ready
The signal relay is active when the pump is running or has
been set to stop, but is ready to run.
Alarm
The signal relay is activated together with the red indicator
light on the pump.
Operation
The signal relay is activated together with the green indicator
light on the pump.
13.7 Setpoint influence
Navigation
Home > Settings > Setpoint influence
Setpoint influence
External setpoint function
Temperature influence.
13.7.1 External setpoint function
The external setpoint function is an external 0-10 V or 4-20 mA
signal that will control the pump speed in a range from 0 to 100 %
in a linear function. See fig. 32.
Fig. 32 External setpoint function, 0-10 V
13.7.2 Temperature influence
When this function is enabled in proportional- or
constant-pressure control mode, the setpoint for head will be
reduced according to the liquid temperature.
Temperature influence can be set to function at liquid
temperatures below +176 °F or +122 °F (80 °C or 50 °C). These
temperature limits are called T
max.
. The setpoint is reduced in
relation to the head set (= 100 %) according to the characteristics
below.
Fig. 33 Temperature influence
In the above example, T
max.
= +176 °F (+80 °C) has been
selected.
The actual liquid temperature T
actual
causes the setpoint for head
to be reduced from 100 % to H
actual
.
The temperature influence function requires the following:
Proportional-pressure, constant-pressure or constant-curve
control mode.
Pump installed in flow pipe.
System with flow-pipe temperature control.
Temperature influence is suitable for the following systems:
Systems with variable flows (for example two-pipe heating
systems) in which the enabling of the temperature influence
function will ensure a further reduction of the pump
performance in periods with small heating demands and
consequently a reduced flow-pipe temperature.
Systems with almost constant flows (for example one-pipe
heating systems and underfloor heating systems), in which
variable heating demands cannot be registered as changes in
the head as is the case with two-pipe heating systems. In such
systems, the pump performance can only be adjusted by
enabling the temperature influence function.
Selection of T
max.
In systems with a dimensioned flow-pipe temperature of:
up to and including +131 °F (+55 °C),
select T
max.
= +122 °F (+50 °C)
above +131 °F (+55 °C), select T
max.
= +176 °F (80 °C).
3.1.15.0.0.0 Setpoint influence
Range
4-20 mA [0-100 %]
0-10 V [0-100 %]
Control
0-20 % (e.g. 0-2 V) Setpoint = Min.
20-100 % (e.g. 2-10 V) Setpoint = Min. setpoint
Note
Note
Before the "
External setpoint function
" can be
enabled, the analog input must be set to
"
External setpoint influence
" via the "
Assist
" menu.
See section 5.5.3 Analog input.
TM05 3219 1212
rpm
V
Min.
02
Max.
10
TM05 7946 1613
Note
Note
The temperature influence function cannot be
used in air-conditioning and cooling systems.
H
T [°F]
30 %
68 122 176
T [°C]
20 50 80
100 %
H
actual
T
actual
H
Q