User Guide
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. General information
- 3. Receiving the product
- 4. Installing the product
- 5. Starting up the product
- 6. Handling and storing the product
- 7. Product introduction
- 8. Control functions
- 9. Setting the product
- 10. Servicing the product
- 11. Fault finding the product
- 12. Technical data
- 13. Accessories
- 14. Disposing of the product
- Français (CA)
- 1. Garantie limitée
- 2. Informations générales
- 3. Réception du produit
- 4. Installation du produit
- 4.1 Lieu d'installation
- 4.2 Outils
- 4.3 Coquilles d'isolation
- 4.4 Installation mécanique
- 4.5 Positionnement du circulateur
- 4.6 Positions du boîtier de commande
- 4.7 Position de la tête du circulateur
- 4.8 Modification de la position du boîtier de commande
- 4.9 Installation électrique
- 4.10 Branchement du câble de l'alimentation électrique
- 5. Démarrage du produit
- 6. Manutention et stockage du produit
- 7. Introduction au produit
- 8. Fonctions de régulation
- 8.1 Aperçu rapide des modes de régulation
- 8.2 Modes de fonctionnement
- 8.3 Modes de régulation
- 8.4 Fonctionnalités supplémentaires pour les modes de régulation
- 8.5 Modes circulateurs multiples
- 8.6 Valeurs de réglage pour les modes de régulation
- 8.7 Précision de l'estimation du débit
- 8.8 Tableau de la précision du débit
- 8.9 Branchements externes
- 8.10 Priorité des réglages
- 8.11 Communication entrée et sortie
- 9. Réglage du produit
- 10. Maintenance du produit
- 11. Détection des défauts de fonctionnement du produit
- 12. Caractéristiques techniques
- 13. Accessoires
- 14. Mise au rebut du produit
- Español (MX)
- 1. Garantía limitada
- 2. Información general
- 3. Recepción del producto
- 4. Instalación del producto
- 5. Puesta en marcha del producto
- 6. Manejo y almacenamiento del producto
- 7. Introducción de producto
- 8. Funciones de control
- 8.1 Breve resumen de los modos de control
- 8.2 Modos de operación
- 8.3 Modos de control
- 8.4 Otras funciones de los modos de control
- 8.5 Modos multibomba
- 8.6 Ajustes de los modos de control
- 8.7 Precisión de la estimación del caudal
- 8.8 Tabla de precisión del caudal
- 8.9 Conexiones externas
- 8.10 Prioridad de los ajustes
- 8.11 Comunicación de entrada y salida
- 9. Ajuste del producto
- 10. Mantenimiento y servicio del producto
- 11. Búsqueda de fallas del producto
- 12. Datos técnicos
- 13. Accesorios
- 14. Eliminación del producto
- Appendix
English (US)
50
9.6.9 "Bus communication"
Navigation
"Home" > "Settings" > "Bus communication"
This menu offers the following options:
• Pump number
• Forced local mode
"Pump number"
Navigation
"Home" > "Settings" > "Bus communication" > "Pump number"
Setting
1. Press [OK] to start the setting. The pump allocates a unique
number to the pump.
The unique number enables you to distinguish between the
pumps in connection with bus communication.
"Forced local mode"
Navigation
"Home" > "Settings" > "Bus communication" > "Forced local
mode"
Setting
To enable the function, choose "Enable" with or and press
[OK]. To disable the function, choose "Disable" with or and
press [OK].
You can temporarily override remote commands from a building
management systems to make local settings. Once you have
disabled "Forced local mode
", the pump reconnects to the
network when it receives a remote command from the building
management system.
"Multipump profile selection"
Navigation
"Home" > "Settings" > "Bus communication" > "Multipump profile
selection"
This menu offers the following options:
• Compatibility for models A, B, C
• Generic Grundfos profile
• Automatic.
Setting
Select mode with and and press [OK].
The MAGNA3 model D pump is able to automatically detect and
adjust itself to an existing system with older version pumps or an
older BMS. You enable this function by choosing "Automatic" in
the display.
"Generic Grundfos profile" overrules auto detection, and the
pump runs as a model D. However, if your BMS system or
existing pumps are older versions, we recommend that you
choose either "Automatic" or "Compatibility for models A, B, C".
See section 13.2.4 Auto detection of CIM modules for further
information on auto detection.
3.1.18.3.0.0 - Settings_BusCommunication3.1.18.1.0.0 Pump number3.1.18.2.0.0 Forced local mode
3.1.18.3.0.0 - Settings_BusCommunication_Multi...
Multipump profile mode must be chosen from the
pump assigned as master.