User Guide
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. General information
- 3. Receiving the product
- 4. Installing the product
- 5. Starting up the product
- 6. Handling and storing the product
- 7. Product introduction
- 8. Control functions
- 9. Setting the product
- 10. Servicing the product
- 11. Fault finding the product
- 12. Technical data
- 13. Accessories
- 14. Disposing of the product
- Français (CA)
- 1. Garantie limitée
- 2. Informations générales
- 3. Réception du produit
- 4. Installation du produit
- 4.1 Lieu d'installation
- 4.2 Outils
- 4.3 Coquilles d'isolation
- 4.4 Installation mécanique
- 4.5 Positionnement du circulateur
- 4.6 Positions du boîtier de commande
- 4.7 Position de la tête du circulateur
- 4.8 Modification de la position du boîtier de commande
- 4.9 Installation électrique
- 4.10 Branchement du câble de l'alimentation électrique
- 5. Démarrage du produit
- 6. Manutention et stockage du produit
- 7. Introduction au produit
- 8. Fonctions de régulation
- 8.1 Aperçu rapide des modes de régulation
- 8.2 Modes de fonctionnement
- 8.3 Modes de régulation
- 8.4 Fonctionnalités supplémentaires pour les modes de régulation
- 8.5 Modes circulateurs multiples
- 8.6 Valeurs de réglage pour les modes de régulation
- 8.7 Précision de l'estimation du débit
- 8.8 Tableau de la précision du débit
- 8.9 Branchements externes
- 8.10 Priorité des réglages
- 8.11 Communication entrée et sortie
- 9. Réglage du produit
- 10. Maintenance du produit
- 11. Détection des défauts de fonctionnement du produit
- 12. Caractéristiques techniques
- 13. Accessoires
- 14. Mise au rebut du produit
- Español (MX)
- 1. Garantía limitada
- 2. Información general
- 3. Recepción del producto
- 4. Instalación del producto
- 5. Puesta en marcha del producto
- 6. Manejo y almacenamiento del producto
- 7. Introducción de producto
- 8. Funciones de control
- 8.1 Breve resumen de los modos de control
- 8.2 Modos de operación
- 8.3 Modos de control
- 8.4 Otras funciones de los modos de control
- 8.5 Modos multibomba
- 8.6 Ajustes de los modos de control
- 8.7 Precisión de la estimación del caudal
- 8.8 Tabla de precisión del caudal
- 8.9 Conexiones externas
- 8.10 Prioridad de los ajustes
- 8.11 Comunicación de entrada y salida
- 9. Ajuste del producto
- 10. Mantenimiento y servicio del producto
- 11. Búsqueda de fallas del producto
- 12. Datos técnicos
- 13. Accesorios
- 14. Eliminación del producto
- Appendix
23
English (US)
8.2 Operating modes
Normal
The pump runs according to the selected control mode.
Stop
The pump stops.
Min.
You can use the minimum curve mode in periods in which a
minimum flow is required. This operating mode is for instance
suitable for manual night setback if automatic night setback is not
desired.
Max.
You can use the maximum curve mode in periods in which a
maximum flow is required. This operating mode is for instance
suitable for hot-water priority.
Fig. 22 Maximum and minimum curves
8.3 Control modes
8.3.1 Factory setting
The pumps have been factory-set to AUTO
ADAPT
without
automatic night setback, which is suitable for most installations.
The setpoint has been factory-set. See section 8.6 Setting values
for control modes.
8.3.2 AUTO
ADAPT
We recommend the AUTO
ADAPT
control mode for most heating
systems, especially in systems with relatively large pressure
losses in the distribution pipes, and in replacement situations
where the proportional-pressure duty point is unknown.
This control mode has been developed specifically for heating
systems and we do not recommend it for air-conditioning and
cooling systems.
Characteristics and key benefits
• Automatically adjusts the pump to actual system
characteristics.
• Ensures minimum energy consumption and a low noise level.
• Reduced operating costs and increased comfort.
Technical specifications
Fig. 23 AUTO
ADAPT
control
The AUTO
ADAPT
control mode is a form of proportional-pressure
control where the control curves have a fixed origin, H
auto_min
.
When you have enabled AUTO
ADAPT
, the pump will start with the
factory setting, H
fac
= H
set1
, corresponding to approx. 55 % of its
maximum head, and then adjust its performance to A
1
. See fig.
23.
When the pump registers a lower head on the maximum curve,
A
2
, the AUTO
ADAPT
function automatically selects a
correspondingly lower control curve, H
set2
. If the valves in the
system close, the pump adjusts its performance to A
3
. See fig.
23.
You can select the control mode and setpoint even if
the pump is not running in Normal mode.
TM05 2446 5111
H
Q
Max.
Min.
TM05 2452 1312
A
1
: Original duty point.
A
2
: Lower registered head on the maximum curve.
A
3
: New duty point after AUTO
ADAPT
control.
H
set1
: Original setpoint setting.
H
set2
: New setpoint after AUTO
ADAPT
control.
H
fac
: See page 29.
H
auto_min
: A fixed value of 1.5 m.
Manual setting of the setpoint is not possible.
H
Q
H
auto_min
A
1
A
3
A
2
H
set1
H
set2