Installation Instructions

14
In the unlikely event that instant hot water is not
available, the circulator impeller may be blocked by
calcium/sediment deposits. Follow these steps to
clean the impeller:
11..
Isolate the circulator from the system water pres-
sure by closing the valves on either side of the circula-
tor. If the circulator cannot be isolated, it will be nec-
essary to turn off the main water supply.
22..
Turn off the power supply.
33..
Loosen the brass ring holding the circulator head to
the pump housing. Be careful a small amount of hot
water may still leak from the connection
44..
Remove the circulator body from the pump housing.
55..
Remove the impeller assembly from the circulator
body by pulling gently upward.
66..
Clean the impeller assembly using water and a
brush.
77..
Remove calcium/sediment deposits from the
impeller passages.
88..
Re-assemble the circulator by reversing steps 1-5
above.
COMFORT PUMP