Installation Instructions

The aquastat is an integrated adjustable thermostat
controlled by the temperature dial. The aquastat allows
the circulator to automatically turn off (the green LED is
off) when the water temperature passing through the
circulator housing reaches the dial setting selected
between 95 deg F and 150 deg F. The circulator will
automatically turn back on (the green LED is on) when
the water temperature cools down 12 deg F.
Setting the aquastat:
11..
The factory preset dial position is 95 deg F.
22..
To increase the temperature setting turn the dial
clockwise.
33..
Turning the dial fully clockwise to the stop defeats
the aquastat function and the circulator will not shut
off by water temperature. It is recommended that this
setting only be used to sanitize/flush the hot water
line.
NNoottee::
140 deg F water is the maximum
recommended fluid temperature to prevent calcium
precipitation in the system.
WWAARRNNIINNGG::
120 deg F water is the maximum
recommended fluid temperature to prevent scalding.
10