Brochure

Table Of Contents
Curve charts and technical data
UP, UPS Series 200
9
56
UPS 80-160/2, 3 ph, 208-230 V, 460 V, 575 V
, 60 Hz
Note: ETA is calculated as wire-to-water efficiency.
Dimensions
Product numbers Connections
Electrical data
TM00 9508 00307
Flow range: 30 - 275 gpm
Head range: 1 - 49 ft
Motor: 2-pole 3.00 Hp
Max. liquid temp (Open): +140 °F
Max. liquid temp.: +248 °F
Min. liquid temp.: +32 °F
Max. system pressure: 145 psi
Net wt: 85.1 lbs (38.6 kg)
Gross wt.: 97.4 lbs (44.2 kg)
Shipping volume: 2.90 ft
3
(0.082 m
3
)
Net wt. bronze: 97.2 lbs (44.1 kg)
Gross wt. bronze: 109.6 lbs (49.7 kg)
Shipping volume bronze: 2.90 ft
3
(0.082 m
3
)
0 50 100 150 200 250 300 Q [US GPM]
0
10
20
30
40
50
H [ft]
0
2
4
6
8
10
12
14
H [m]
0 10 20 30 40 50 60
Q [m³/h]
1
2
3
0 50 100 150 200 250 300 Q [US GPM]
0
1000
2000
3000
P1 [W]
0
20
40
60
Eta [%]
0
1
2
3
4
P1 [hp]
3
2
1
Eta
TM02 0731 5100
B2
NPT 1/4
B1
H2
H1
H3
M
D5
D4
D3
D2
D1
B7
B4
B5
L1
L3
Model L1L3B1B2B4B5B7H1H2H3D1D2D3D4D5D6D7 M
UPS 80-160/2
[in] 19.00 9.50 5.75 6.68 3.94 3.94 6.31 3.81 11.31 15.20 3.19 5.00 6.00 7.56 0.75
[mm] 483 241 146 170 100 100 160 97 287 386 81 127 152 192 19 M16
Model type
Product number
Voltage
[V]
Cast Iron Bronze
UPS 80-160/2
(3 ph)
96402920 96402923 208-230
96402921 96402924 460
96402922 96402925 575
Flange size Flange type
3" ANSI 125# R.F. GF80
Speed
Max amps
[A]
P Max
[Watts]
Start amps
[A]
All 3-phase, 460V and 575V pumps are 2-speed only.
Canada only.
208-230V 460V 575V 208-230V 460V 575V
3 6.35 3.13 2.54 2050 31.00 15.40 12.32
2 4.20 2.10 1.68 1550 20.50 10.17 8.14
14.05▲▲1500 19.77 ▲▲
UP 80-160/2
3 ph, 208-230 V, 460 V, 575 V
, 60 Hz