Brochure
Table Of Contents
- 1. Product introduction
- 2. Product overview
- 3. Product range
- 4. Cross-reference guide
- 5. Construction
- 6. Operating conditions
- 7. Functions
- 8. Technical data
- 9. Curve charts and technical data
- UPS 32-40/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 32-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 32-80/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 32-80/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 32-160/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 32-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-40/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-80/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-80/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-80/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-80/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-160/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-240/2, 1 ph, 230 V, 60 Hz
- UPS 40-240/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-40/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 50-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-80/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 50-80/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-80/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 50-80/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-160/2, 1 ph, 230 V, 60 Hz
- UPS 50-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-240/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 53-55/57, 1 ph, 115 V, 230 V, 60 Hz
- UPS 53-55/57, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 75-69/2, 1 ph, 230 V, 60 Hz
- UPS 75-69/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 80-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 80-80/4, 3 ph, 208-230 V, 60 Hz
- UPS 80-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 100-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UP 43-70, 1 ph, 115 V / 230 V, 60 Hz
- UP 43/110, 1 ph, 115 V / 230 V, 60 Hz
- UP 53-45, 1 ph, 115 V / 230 V, 60 Hz
- UP 53-46, 1 ph, 115 V / 230 V, 60 Hz
- 10. Accessories and spare parts
- 11. Further documentation
Operating conditions
UP, UPS Series 200
6
14
Electrical data
Supply voltage and frequency
UPS: 115 V, 230 V, 1-phase 60 Hz, 208-230 V, 460 V,
575 V, 3 phase 60 Hz.
UP: 115 V, 230V, 1-phase 60 Hz, 460 V, 575 V,
3-phase 60Hz.
Back-up fuse: Max. 10 A.
Enclosure class: IP 44 indoor use only.
Supply voltage tolerances
The motors meet the requirements to temperature rise
at - 6 / +6 %.
Furthermore, the motors have been tested at
-10 / +10 % of the voltage range. During these tests,
the motors operate without problems and without being
thermally cut out.
The motor voltage tolerances are intended for power
supply voltage variations. They should not be used for
running motors at other voltages than those stated on
the name plates.
Variable speed applications
All 3 x 460 V, 3 x 575 V and 3-speed 3 x 208-230 V
pumps with standard module are suitable for frequency
converter applications. Please refer to section Variable
frequency drive operation on page 17 for
further information.
Terminal box
Fig. 6 Terminal box
The terminal box with cover (pos. 1) is made from
black composite material.
The terminal box is equipped with:
• 1 x 1½" NPT screwed cable entry for mains
connection, to be fitted during installation.
• 1 x M16 screwed cable entry for capacitor
connection (only single-phase pumps)
• 2 x indicator lights (single-phase pumps with
standard module have just one).
Note: UPS pumps only.
• window for indication of speed.
Note: UPS pumps only.
The terminal box is fastened to the stator housing with
screws and connected to the stator by a terminal plug.
Insulation class
Thermal overload switch
Start/stop input (relay module)
External potential-free contact.
Maximum load: 250 V, 1.5 mA.
Minimum load: 100 V, 0.5 mA.
Operating/fault signal output (relay module)
Internal potential-free changeover contact.
Maximum load: 250 V, 2 A, AC.
Minimum load: 5 V, 100 mA, DC.
TM00 9133 4596
Indicator lights and speed
indication
Pump type Insulation class
UPS
1 x 115 V
1 x 230 V
3 x 208-230 V
3 x 460 V
3 x 575 V
32-40 F F
32-80 F F
32-160 H F
40-40 F F
40-80/4 H H
40-80/2 F F
40-160 H H
40-240 H H
50-40 F F
50-80/4 H H
50-80/2 H F
50-160 H H
50-240 — H
53-55/57 H F
75-69 H H
80-40 — H
80-80 — H
80-160 — H
100-40 — H
Pump type Insulation class
UP 1 x 115/230 V
43-70 F
43-110 F
53-45 F
53-46 F
Voltage 250 V AC
Current
cos phi = 1.0: 2.5 A
cos phi = 0.6: 1.6 A