Brochure
Table Of Contents
- 1. Product introduction
- 2. Product overview
- 3. Product range
- 4. Cross-reference guide
- 5. Construction
- 6. Operating conditions
- 7. Functions
- 8. Technical data
- 9. Curve charts and technical data
- UPS 32-40/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 32-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 32-80/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 32-80/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 32-160/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 32-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-40/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-80/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-80/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-80/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-80/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-160/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 40-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 40-240/2, 1 ph, 230 V, 60 Hz
- UPS 40-240/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-40/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 50-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-80/4, 1 ph, 115 V, 230 V, 60 Hz
- UPS 50-80/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-80/2, 1 ph, 115 V, 230 V, 60 Hz
- UPS 50-80/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-160/2, 1 ph, 230 V, 60 Hz
- UPS 50-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 50-240/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 53-55/57, 1 ph, 115 V, 230 V, 60 Hz
- UPS 53-55/57, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 75-69/2, 1 ph, 230 V, 60 Hz
- UPS 75-69/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 80-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 80-80/4, 3 ph, 208-230 V, 60 Hz
- UPS 80-160/2, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UPS 100-40/4, 3 ph, 208-230 V, 460 V, 575 V«, 60 Hz
- UP 43-70, 1 ph, 115 V / 230 V, 60 Hz
- UP 43/110, 1 ph, 115 V / 230 V, 60 Hz
- UP 53-45, 1 ph, 115 V / 230 V, 60 Hz
- UP 53-46, 1 ph, 115 V / 230 V, 60 Hz
- 10. Accessories and spare parts
- 11. Further documentation
Functions
UP, UPS Series 200
7
17
Fig. 12 1 x 115/230 V terminal box
The voltage is changed by changing the orientation of
the jumpers. See fig. 12.
The pump must be connected to the power supply via
an external switch.
The UP pumps are equipped with a built-in, automati-
cally resetting terminal overload switch, protecting the
pump at both 115 V and 230 V. The built-in terminal
overload switch (terminals P1 and P2) can optionally
be connected to external overload protection.
Pumps with standard module
Fig. 13 Terminal box with standard module
The standard module is standard in three-phase
pumps with three speeds and forms connection
between supply terminals and motor.
The pumps with standard module must be connected
to the power supply via an external contactor.
For motor protection the contactor is to be connected
to the pump’s built-in thermal overload switch to
protect the pump against overheating at all three
speeds.
Standard module indicator lights
The indicator lights on pumps with standard module
show whether the pump is live, or whether the phase
sequence of three-phase pumps is wrong.
Single-phase pumps
Single-phase pumps incorporate a green indicator light
only:
Three-phase pumps
Three-phase pumps have a green and a red indicator
light:
Variable frequency drive operation
All 3 x 460 V, 3 x 575 V and 3-speed 3 x 208-230 V
pumps with standard module are suitable for variable
frequency drive (VFD) applications. Please note the
following:
• Even if the red indicator light is on, the pump is
operating normally.
• Pumps fitted with other modules than the standard
module must not be connected to a VFD.
• Depending on the VFD type, this may cause
increased acoustic noise from the motor.
Furthermore, it may cause the motor to be exposed
to detrimental voltage peaks.
• The motor must be protected against voltage peaks
higher than 650 V between the motor terminals.
Acoustic noise and detrimental voltage peaks can be
reduced by fitting an LC filter between the VFD and the
motor.
Pumps with protection module
The protection module is standard for single-phase
UPS pumps and available for 3 x 208-230 V UPS
pump models only as an option.
When fitted with a protection module, the pump can be
connected directly to the power supply switch as it will
be protected by the built-in overload protection.
The protection module incorporates two indicator
lights.
TM02 5761 3902TM00 9237 4597
P1
P2
T8
T4
T5
T1
T2
T3
LN
Jumpers
Standard module
Speed switch
Indicator light Description
On The electricity supply has been switched on.
Off
The electricity supply has been switched off, or
the pump has been cut out by the thermal
overload switch.
Indicator lights
Description
Green Red
Off Off
The electricity supply has been switched off, or the
pump has been cut out by the thermal overload
switch.
On Off The electricity supply has been switched on.
On On
The electricity supply has been switched on.
The direction of rotation is wrong.