Brochure

GRUNDFOS CONTROL PANELS
Simplex
Panel
Duplex
Panel
Standard Features
LISTING: Underwriters Laboratories, UL 508.
RATINGS: Model S1 rated up to 120 VAC, 1 Hp, 16 A, Single Phase, 60 Hz.
Model S2 rated at 230 VAC, 1-1/2 Hp, 16 A, Single Phase, 60 Hz.
MOTOR-START CONTRACTOR: Rated for 24 FLA, Single Phase, 60 Hz.
CURRENT LIMITING CIRCUIT BREAKER: 20 amp, OFF/ON switch, DIN rail
mounting with thermal magnetic tripping characteristics. (Single Pole/
120 V; Double Pole/240V)
TOGGLE SWITCH: A SPDT HOA switch with a 10 A 115V/20A 230V motor
rating.
FUSE DISCONNECT: 5 amp (10,000 AIC) fuse with DIN rail mount.
AUDIBLE ALARM: Panel mount with a minimum of 80 db sound pres-
sure at 24 inches, warble tone sound.
VISUAL ALARM: NEMA 4-rated, 7/8 inch diameter, red lens, oil-tight
with push-to-silence feature.
AUDIO-ALARM SILENCE RELAY: 120 VAC, automatic reset, with DIN rail
mount socket base.
ALARM CIRCUIT: 120 VAC, wired separately from pump circuit, so that if
the pump’s internal overload switch or current-limiting circuit breaker
is tripped the alarm system remains functional.
ENCLOSURE: NEMA 4X-rated, fiberglass with hinged cover.
Noncorroding. External mounting ears.
PADLOCKABLE LATCH: Constructed of noncorroding stainless steel.
Standard Features
LISTING: Underwriters Laboratories, UL 508 Listed.
RATINGS: Model D1 rated up to 120 VAC, 1 Hp, 16 A, Single Phase,
60 Hz.
Model D2 rated at 240 VAC, 1-1/2 Hp, 16 A, Single Phase, 60 Hz.
MOTOR-START CONTRACTOR: Rated for 24 FLA, Single Phase,
60 Hz.
CURRENT LIMITING CIRCUIT BREAKER: 20 amp, OFF/ON switch, DIN rail
mounting with thermal magnetic tripping characteristics. (Single Pole/
120 V; Double Pole/240V)
TOGGLE SWITCH: A SPDT HOA switch with a 20 amp motor rating.
FUSE DISCONNECT: 5 amp (10,000 AIC) fuse with DIN rail mount.
DUPLEX ALTERNATOR: Cross wired style for independent lag pump func-
tion.
AUDIBLE ALARM: Panel mount with a minimum of 80 db sound pres-
sure at 24 inches, warble tone sound.
VISUAL ALARM: NEMA 4-rated, 7/8 inch diameter, red lens, oil-tight with
push-to-silence feature.
AUDIO-ALARM SILENCE RELAY: 120 VAC, automatic reset, with DIN rail
mount socket base.
ALARM CIRCUIT: Wired separately from pump circuit, so that if the
pump’s internal overload switch or current-limiting circuit breaker is
tripped the alarm system remains functional.
ENCLOSURE: NEMA 4X-rated, fiberglass with hinged cover.
Noncorroding. External mounting ears.
PADLOCKABLE LATCH: Constructed of noncorroding stainless steel.
Dimensions
Dimensional
Drawing
Sensor Floats
Part Number Panel Type Model Phase Voltage Horsepower A B C D E
96001030 10’
96001031 20’
96001032 Simplex S1 1 115
1
/
3
- 1 9
5
/
16
11
5
/
16
11
1
/
2
10
3
/
4
5
1
/
2
96001040 Simplex S2 1 230
1
/
3
- 1
1
/
2
9
5
/
16
11
5
/
16
11
1
/
2
10
3
/
4
5
1
/
2
96001033 Duplex D1 1 115
1
/
3
- 1 13
5
/
16
15
5
/
16
15
1
/
2
14
3
/
4
8
1
/
4
96001041 Duplex D2 1 230
1
/
3
- 1
1
/
2
13
5
/
16
15
5
/
16
15
1
/
2
14
3
/
4
8
1
/
4
Part Number Length