Technical data and performance curves
Unilift CC, KP, AP
3
13
Performance curves
Installation
Pumps without float switch can be used in vertical
position with the discharge port pointing upwards or in
horizontal or tilted position with the discharge port as
the highest point of the pump.
Fig. 7 Pump positions
Adjustment of cable length for float
switch
A clamp on the pump handle holds the float switch
cable. The difference in level between start and stop
can be adjusted by changing the free cable length
between the pump handle and the float switch.
Fig. 8 Start-stop level, Unilift KP
The start/stop level varies according to the cable
length.
TM04 2409 2508
0 5 10 15 20 25 30 35 40 45 50 55 60 Q [US GPM]
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
[ft]
H
0 2 4 6 8 10 12 14 Q [m³/h]
Unilift KP
60 Hz
250
150
350
TM00 1548 0493
TM03 4331 2006
Cable length
Min. 2.5"
Cable length
Max. 6"
Start Stop Start Stop
Unilift KP 150
Unilift KP 250
11.5" 5.5" 12.5" 3.5"
Unilift KP 350 12" 6" 13 4"
••••••••••••••
••••••••••••
•••••••••••
••••••••••••
•••••••••••
••••••••••
•••••••••••
••••••••••
••••••••••
••••••••••
•••••••••
••••••••
••••••••
Start
Stop
Min./max. cable length