User Guide

24
21. Installation in the USA and Canada
In order to maintain the UL/cUL approval, these additional
installation procedures must be followed. The UL approval is
according to UL508C.
21.1 Electrical installation
21.1.1 Conductors
Use 140/167°F (60/75°C) copper conductors only.
21.1.2 Torques
Power terminal, M4: 2.35 Nm.
Relay, M2.5: 0.5 Nm.
Input control, M2: 0.2 Nm.
21.1.3 Overload protection
Degree of overload protection provided internally by the drive, in
percent of full-load current: 102%.
21.2 Before starting the pump
The pump must always be connected to the power supply at
least one hour prior to start.
From then on the pump must always be connected to the
power supply.
This procedure will help to avoid condensation in the terminal
box.
Subject to alterations.