Submittal Sheet
Company name:
Created by:
Phone:
Fax:
Date:
-
-
-
-
-
-
-
-
-
-
Printed from Grundfos CAPS [2011.05.069]
Position Count Description Unit price
- sensor, 0 - 5 V, 0 - 10 V, 0(4) - 20 mA,
- 24 V voltage supply for sensor, Imax = 40 mA,
- input for forced control to MIN or MAX
(potential-free contact),
- potential-free fault signal relay with
changeover contact,
- RS485 GENIbus.
Liquid:
Liquid temperature range: 5 .. 284 °F
Liquid temp: 68 °F
Technical:
Actual calculated flow: 161 US gpm
Resulting head of the pump: 49.8 ft
Shaft seal: BUBE
Maximum operating pressure: 145 psi
Materials:
Pump housing: Cast iron
EN-JL 1040
ASTM 25 B
Impeller: Stainless steel
DIN W.-Nr. 1.4301
AISI 304
Installation:
Maximum ambient temperature: 104 °F
Maximum operating pressure: 145 psi
Flange standard: ANSI
Pipe connection: 3"
Pressure stage: Class 125
Flange size for motor: 182TC
Electrical data:
Motor type: 90FA
Number of poles: 2
Rated power - P2: 3 HP
Main frequency: 60 Hz
Rated voltage: 3 x 208-230 V
Rated current: 8.3 A
Cos phi - power factor: 0.95
Rated speed: 3460 rpm
Enclosure class (IEC 34-5): 55
Insulation class (IEC 85): F
Others:
Gross weight: 138 lb
2/6