Install Instructions

Page 3
1. Shipment Inspection
Check the contents of this package. Care should be
taken to ensure the pump is NOT dropped or mis-
handled; dropping will damage the pump.
Grundfos MixiMizer Injection Pump Package Includes:
One Grundfos UP15-42 MixiMizer pump with
integral control or one Grundfos UP43-64
MixiMizer pump with integral control.
Two Water Temperature Sensors 071 – Pre-wired
into control unit with 6’ of wire.
One 6’ line cord with 115 V plug, pre-wired into
control unit.
One Outdoor Air Temperature Sensor 070
Two flange gaskets
Installation and Operating Instructions.
Two cable ties.
2. General
All minimum and maximum settings are operating,
not safety limits. Necessary auxiliary equipment
and safety devices must be added.
The boiler return minimum temperature is fixed at
135°F. This function can be disabled by DIP
switch.
The system supply maximum temperature is fixed
at 140°F. This function can be disabled by DIP
switch.
External “Call For Heat”/Demand Input: The unit
can accept external “Call For Heat” input signal.
This must be a powered signal (20 to 30 V AC .1
VA). This function can be enabled by DIP switch.
Warm Weather Shut Down (WWSD): When the
outdoor air temperature is warmer than 70°F (with
±1°F hysteresis), the unit shuts down until the
temperature drops below 70°F.
Heating curve parallel shift: The heating curve is
shifted up 5°F parallel to the existing curve. This
function can be enabled by the dip switch.