SQFlex data booklet

Table Of Contents
CU 200 SQFlex control unit
CU 200 is a combined status, control and communication
unit designed for the SQFlex system. It can be connected to
a level switch and is designed for SQFlex power range up to
1400 W and maximum 8.4 A.
CU 200 incorporates cable entries for the following
connections:
power supply (pos. 6)
pump (pos. 7)
earth (pos. 8)
level switch (pos. 9).
The communication between CU 200 and the pump is
ensured through the power supply cable. This is called
mains-borne signaling (or power line communication), which
does not require extra cables between CU 200 and the
pump.
Start, stop and reset the pump with the ON/OFF button
(pos. 1).
CU 200 ensures system monitoring and alarm indication.
The operation can be monitored through the following
indications:
water reservoir full (level switch) (pos. 2)
pump running (pos. 3)
input power (pos. 11).
CU 200 indicates the following alarms:
dry running (pos. 10)
service needed (pos. 5):
- no contact to the pump
- overvoltage
- overtemperature
- overload.
In addition, CU 200 shows the symbols of the energy supply
options (pos. 4).
6
10
3
4
2 1
11
987
5
TM022325
CU 200 elements
kWatt
199mm (7.83 in)
263 mm (10.35 in)
95 mm
(3.75 in)
TM078601
Dimensions, CU 200
GND IN
F1 = OVERVOLTAGE
F2 = OVERTEMP
F3 = NO CONTACT
F4 = OVERLOAD
CONTROL INDICATOR
MAX SPEED
+24 V
+10 V
+5 V
LEVEL SWITCH
POWER PUMP
PE PE PE
GND IN
F1 = OVERVOLTAGE
F2 = OVERTEMP
F3 = NO CONTACT
F4 = OVERLOAD
CONTROL INDICATOR
MAX SPEED
+24 V
+10 V
+5 V
LEVEL SWITCH
TM022515
Electrical connections, CU 200
Level switch input
High water level: Contact is closed.
Low water level: Contact is open.
SQFlex
4
20
System components