Installation and Operating Instructions

Table Of Contents
STATUS-NOT-SET | Code-22-(Moisture-in-motor-of-pump)-(ts)-AKmwWVA.dita
8.6 Code 22 (Moisture in motor of pump)
Alarm code 22 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Moisture in motor of pump is displayed in
Grundfos GO Remote.
Cause Moisture is detected in the motor of the pump.
Remedy Service is needed on the pump. Contact
Grundfos.
STATUS-NOT-SET | Code-25-(Wrong-configuration)-(ts)-ABufzyQ.dita
8.7 Code 25 (Wrong configuration)
Alarm code 25 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Wrong configuration is displayed in Grundfos GO
Remote.
Cause The level control is not configured correctly.
Remedy Check and adjust the level control configuration
with Grundfos GO Remote.
Cause The IO terminal is not configured correctly.
Remedy Select which IO terminal to change in Grundfos
GO Remote and adjust the configuration.
STATUS-NOT-SET | Code-48-(Motor-is-overloaded)-(ts)-AL8bS1s.dita
8.8 Code 48 (Motor is overloaded)
Alarm code 48 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Motor is overloaded is displayed in Grundfos GO
Remote.
Cause
The pump is clogged.
The blockage causes the motor current to rise,
which could damage the pump.
Remedy Remove the blockage.
Check the pit conditions to ensure blockage is
not possible again.
Related information
5.14.2 Overload protection
STATUS-NOT-SET | Code-57-(Missing-water-in-the-application)-(ts)-AEd1sjo.dita
8.9 Code 57 (Missing water in the application)
Alarm code 57 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Dry Run is displayed in Grundfos GO Remote.
Cause
Low water level in the pit and the pump stops
due to the dry-running function.
Remedy Check and configure the sensor for stop level.
STATUS-NOT-SET | Code-69-(Winding-temperature-too-high)-(ts)-ALlcK6Q.dita
8.10 Code 69 (Winding temperature too high)
Alarm code 69 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Winding temperature too high is displayed in
Grundfos GO Remote.
Cause
The pump is clogged, causing the pump to use
more current and thereby overheat.
Remedy Remove the blockage.
Cause The pump has run for too long.
Remedy Allow the pump to cool down.
Adjust the distance between start and stop
levels.
Related information
5.14.1 Overheat protection
STATUS-NOT-SET | Code-84-(Memory-storage-media-faulty)-(ts)-AAFdH3w.dita
8.11 Code 84 (Memory storage media faulty)
Warning code 84 is shown on the display if you press
the Up or Down button.
The warning symbol on the display turns yellow and the pump's
operating mode is unchanged.
Warning code Memory storage media faulty is displayed in
Grundfos GO Remote.
Cause An error in the internal memory has been
detected.
Remedy Replace the control unit.
Contact Grundfos or an authorised service
workshop.
STATUS-NOT-SET | Code-117-(Door-opened)-(ts)-AM3fu5U.dita
8.12 Code 117 (Door opened)
Warning code 117 is shown on the display if you press
the Up or Down button.
The warning symbol on the display turns yellow and the pump's
operating mode is unchanged.
Warning code Door opened is displayed in Grundfos GO
Remote.
Cause
The door to the control-unit room has been
opened.
Remedy Check the room with the control unit.
STATUS-NOT-SET | Code-159-(Communication-error-CIMxxx)-(ts)-AC0zApI.dita
8.13 Code 159 (Communication error CIMxxx)
Warning code 159 is shown on the display if you press
the Up or Down button.
The warning symbol on the display turns yellow and the pump's
operating mode is unchanged.
Warning code Communication error CIMxxx is displayed in
Grundfos GO Remote.
The CIM module is unable to communicate with the product.
Cause
The CIM module is installed incorrectly.
Remedy Ensure that the module, including cables, is
fitted correctly.
Cause The CIM module is defective.
Remedy Contact Grundfos.
STATUS-NOT-SET | Code-165-(Signal-fault)-(ts)-AHFcN8w.dita
8.14 Code 165 (Signal fault)
Alarm code 165 is shown on the display.
The alarm symbol on the display turns red and the pump stops.
Alarm code Signal fault is displayed in Grundfos GO Remote.
Cause
The signal from the sensor is out of the
configured range.
Remedy Go to Settings > Level Control in Grundfos
GO Remote and ensure that the configured
range corresponds to the physical application
type.
Change the sensor, if needed.
15
English (GB)