Installation and Operating Instructions
Table Of Contents
- English (GB)
- 1. General information
- 2. Installing the product
- 3. Starting up the product
- 4. Product introduction
- 5. Control functions
- 5.1 Application types
- 5.2 Setting the sensor type
- 5.3 Setting the start level
- 5.4 Setting the stop level
- 5.5 Setting the high level
- 5.6 Stop delay
- 5.7 Power-on delay
- 5.8 Dry-running protection
- 5.9 Using the same level switch for the start and stop level
- 5.10 "Multipump settings"
- 5.11 "Antiseizing"
- 5.12 Signal detection time
- 5.13 Setting the maximum number of restarts with Grundfos GO Remote
- 5.14 Motor protection
- 5.15 Alarm reset
- 5.16 Setting the buzzer with Grundfos GO Remote
- 5.17 Setting units for Grundfos GO Remote
- 5.18 Setting units for the operating panel with Grundfos GO Remote
- 5.19 GENIbus
- 5.20 Security
- 5.21 Starting the startup wizard with the operating panel
- 6. Operating the product
- 7. Servicing the product
- 8. Fault finding the product
- 8.1 Overview of alarm and warning codes
- 8.2 Code 2 (Power phase missing)
- 8.3 Code 4 (Too many motor restarts)
- 8.4 Code 9 (Power phase sequence wrong)
- 8.5 Code 12 (Service needed)
- 8.6 Code 22 (Moisture in motor of pump)
- 8.7 Code 25 (Wrong configuration)
- 8.8 Code 48 (Motor is overloaded)
- 8.9 Code 57 (Missing water in the application)
- 8.10 Code 69 (Winding temperature too high)
- 8.11 Code 84 (Memory storage media faulty)
- 8.12 Code 117 (Door opened)
- 8.13 Code 159 (Communication error CIMxxx)
- 8.14 Code 165 (Signal fault)
- 8.15 Code 191 (High water level)
- 8.16 Code 205 (Level switch inconsistency)
- 8.17 Code 225 (Communication error pump module)
- 8.18 Code 226 (Communication error IO module)
- 8.19 Code 229 (Water on floor)
- 9. Technical data
- 10. Disposing of the product
A lock symbol indicates which menus are locked. To view or change
settings, you must enter the PIN code.
STATUS-NOT-SET | Unlocking-Grundfos-GO-Remote-(ta)-0pI-a9o.dita
5.20.4 Unlocking Grundfos GO Remote
1. Go to Settings > Security.
2. Enter the four digit PIN code.
3. Select Go Remote Security.
4. Select Disabled and press Next.
All menus in Grundfos GO Remote are unlocked.
STATUS-NOT-SET | Starting-the-setup-wizard-with-the-operating-panel-(ta)--YZpWCQ.dita
5.21 Starting the startup wizard with the operating panel
• Press and hold the OK button for 8 seconds until S-1 or S-2
starts flashing.
Related information
3.1.3 Startup wizard on the operating panel
6. Operating the product
6.1 Manual operation
STATUS-NOT-SET | Starting-and-stopping-the-pump-manually-with-Grundfos-GO-Remote-(ta)--qbI-DY.dita
6.1.1 Starting and stopping the pump manually with Grundfos
GO Remote
1. Go to Settings > Control, pump 1 or Control, pump 2.
2. Start the pump by selecting On and pressing OK.
3. Stop the pump by selecting Off and pressing OK.
Related information
6.1.4 Choosing what the pump must do after manual start
STATUS-NOT-SET | Automatic-operation-(co)-zDLyIUk.dita
6.1.2 Automatic operation
In automatic operating mode, the control unit starts and stops the
pump based on the signals it receives from the connected level
sensors and the corresponding level settings within the control unit.
Related information
5.1 Application types
STATUS-NOT-SET | Starting-and-stopping-the-pump-manually-with-the-operating-panel-(ta)--OTUPQc.dita
6.1.3 Starting and stopping the pump manually with the
operating panel
1. To start a pump manually, press and hold the Pump button until
the pump starts.
The On indicator light is lit when the pump is operating in
manual mode.
2. Stop the pump by pressing the Pump button.
The Off indicator light is lit when the pump is stopped.
Related information
6.1.4 Choosing what the pump must do after manual start
STATUS-NOT-SET | Choosing-what-the-pump-must-do-after-manual-start-(ta)--fSAD1s.dita
6.1.4 Choosing what the pump must do after manual start
The following can be configured:
• Automatic return
Here you select if the pump must automatically return to a
defined operating mode when the manual start ends.
• Return to
Here you select whether the pump must return to automatic
operating mode or stop when the manual start ends and
Automatic return has been enabled.
• Forced start time
Here you set the time period in which the pump must run in
manual operating mode.
1. Go to Settings > Manual start.
2. Select Automatic return and choose one of the following
options:
• Disabled
• Enabled.
3. Go one step back in the menu and select
Return to.
4. Choose one of the following options:
• Auto
• Off.
5. Go one step back in the menu and select Forced start time.
6. Set the time period in which the pump must run in manual
operating mode.
Related information
6.1.1 Starting and stopping the pump manually with Grundfos GO
Remote
6.1.3 Starting and stopping the pump manually with the operating
panel
STATUS-NOT-SET | Service-(co)-x-7B76M.dita
7. Servicing the product
DANGER
Electric shock
Death or serious personal injury
‐ Switch off the incoming power supply before you start
any work on the product or connected pumps.
‐ Make sure that the power supply cannot be switched
on accidentally.
STATUS-NOT-SET | Updating-the-product-software-(ta)-zmzYHqU.dita
7.1 Updating the product software
New features and functions can be made available during the
product's life cycle.
1. Contact Grundfos to get your product software updated.
STATUS-NOT-SET | Replacing-the-control-unit-(ta)-IyChqRk.dita
7.2 Replacing the control unit
DANGER
Electric shock
Death or serious personal injury
‐ Switch off the power supply before making any
electrical connections.
‐ Make sure that the power supply cannot be switched
on accidentally.
Remember to save the controllers settings in Grundfos GO Remote
under Settings. The settings can then be transferred to the new
control unit when installed.
1. Switch off the power supply to the product and
other components with external supply.
2. Write down the terminal connection of each wire to ensure
correct re-connection.
3. Disconnect all wires.
4. Remove the control unit from the panel or cabinet.
5. Fit the new unit.
6. Connect all wires.
7. Configure the new control unit using Grundfos GO Remote.
Related information
2.2.1 Mounting the control unit
3.1.2 Startup wizard on Grundfos GO Remote
STATUS-NOT-SET | Replacing-the-CIM-module-(ta)-cYQpf2Y.dita
7.3 Replacing the CIM module
DANGER
Electric shock
Death or serious personal injury
‐ Switch off the power supply before making any
electrical connections.
‐ Make sure that the power supply cannot be switched
on accidentally.
13