Specification
3
Technical Data
September 2014
Dual Relay Switchpack
www.coopercontrol.com
Wiring Diagrams
LOAD "A"
RED (RELAY 2)
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, BOTH
LOADS TURN ON.
2. LOADS TURN OFF WHEN SENSOR
TIMES OUT.
3. SWITCHES CAN BE USED TO TURN
LOADS ON OR OFF.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
NOTES
1. SPD20-MV-NO SWITCHPACK SHOWN.
120/277 VAC 20AMP RATING PER RELAY.
2. BLUE AND RED WIRE LEADS ARE
NON-POLARITY SENSITIVE.
RED (RELAY 2)
BLUE (RELAY 1)
BLUE (RELAY 1)
WHITE
HOT **
LOAD "B"
BLACK (COMMON)
BLACK (COMMON)
BLUE (CONTROL - RELAY 1)
RED (24 VDC)
YELLOW (CONTROL - RELAY 2)
BLUE (CONTROL)
RED (10-30 VDC)
LOAD "A"
RED (RELAY 2)
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
BLACK
BROWN (BLUE CONTROL)
YELLOW (OCC/DAY)
PURPLE (NORMALLY CLOSED)
GRAY (ISOLATED RELAY COMMON)
ORANGE (NORMALLY OPEN)
WHITE/BROWN (YELLOW CONTROL)
BLACK (COMMON)
BLUE (CONTROL - RELAY 1)
RED (24 VDC)
MODEL GMDS - LOAD "A"
(NORMALLY OPEN
MOMENTARY SWITCH)
MODEL GMDS - LOAD "B"
(NORMALLY OPEN
MOMENTARY SWITCH)
MANUAL MODE OPERATION:
1. SWITCHES ARE REQUIRED TO TURN
CORRESPONDING LOADS ON.
2 LOADS TURN OFF WHEN SENSOR
TIMES OUT OR WITH THE SWITCH.
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, BOTH
LOADS TURN ON.
2. SWITCHES CAN BE USED TO TURN
LIGHTS ON OR OFF.
3. IF DAYLIGHT SENSOR IS ENABLED AND
LIGHT LEVEL IS ABOVE SETPOINT,
SWITCHPACK CONNECTED TO YELLOW
LEAD WILL NOT TURN LOAD ON.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
NOTES
1. SPD20-MV-NO SWITCHPACK SHOWN.
120/277 VAC 20AMP RATING PER RELAY.
2. BLUE AND RED WIRE LEADS ARE
NON-POLARITY SENSITIVE.
YELLOW (CONTROL - RELAY 2)
RED (RELAY 2)
BLUE (RELAY 1)
BLUE (RELAY 1)
WHITE
HOT **
LOAD "B"
BLUE (OCC)
RED (10-30 VDC)
SPD20-MV-NO (Line Voltage Switches)
SPD20-MV-NO (Low Voltage Switching)
CAUTION: Before installing or
performing any service on a Greengate
system, the power MUST be turned
OFF at the branch circuit breaker.
*This configuration is for single sensor application only