Installation (cont’d)
Supporting and Mounting
Mount the generator on a concrete slab capable of supporting the weight of the generator. The slab must
extend on all sides beyond the frame by at least one foot. Contact a cement contractor for slab specifications
if necessary. Attach the frame to the concrete slab using 3/8” diameter expansion anchor bolts (not supplied).
Grounding
NOTE: IT IS RECOMMENDED THAT ONLY A TRAINED AND LICENSED
ELECTRICIAN PERFORM THIS PROCEDURE
Connect a #6 AWG grounding wire (not included) from the ground connector (8) on the generator to a
grounding rod (not included) that has been driven at least 24 inches deep into the earth. The grounding rod
must be an earth-driven copper or brass rod (electrode) which can adequately ground the generator.