Installation Guide

INSTALLATION
7
3.4 Condensate Drain……………………………………………………………...
CONDENSATE DRAIN LINE CONNECTION
Remove condensate drain line cover to access primary and secondary drain line connections.
Remove the 3/4" male threaded plug in order to field install a 3/4" I.D. copper or PVC adapter
fitting, P-trap, and drain line to allow for the condensate drainage during the cooling mode
operation.
NOTE:
It is the licensed HVAC installing contractors responsibility to install the condensate drain
line in accordance with any prevailing local, state, and federal codes and regulations.
P-trap must be deep enough to overcome static
Primary & Secondary pressure while the fan is operating during the
drain line connections: cooling mode operation.
Horizontal Left Horizontal Right
installation installation
Vertical installation
CONDENSATE DRAIN PAN CONFIGURATION
Condensate drain pan is configured from the factory to allow for a Vertical or Horizontal Left
installations. For Horizontal Right installations, remove the condensate drain pan and configure it
to the opposite side of the Indoor Unit as shown below, for all condensate to drain through the
factory drain pan and drain line connection.
Primary & Secondary Condensate
Drain Line Connections
3/4" I.D.