Press the OK, MODE and SET/INFO keys simultaneously for 3 seconds until the installation menu
(INSTALLERS MENu) is displayed Under ExTERNAL INPuT (ExT), you can configure the external
input
Motion detector (DIGI)
If you connect a motion detector to the external input, in the installation menu under ExTERNAL INPuT
(ExT) you have to select the setting MdC (motion detector)
The connection type of the motion detector must be an NO contact
After connection of the motion detector, the room thermostat clock will switch to the Reduced
temperature mode ( + ) If the motion detector detects movement in the room, the room thermostat
clock will automatically switch to the Comfort temperature mode for the next 30 minutes ( + )
If the motion detector detects further movement, before the 30 minutes have expired, the Comfort
temperature mode will be extended by another 30 minutes
If no more movement is detected within the 30 minutes, the room thermostat clock will switch back to
the Reduced temperature mode