Installation Guide

EZ Standing Seam Roof
Mounting System
20 | P a g e
Minimum Panel Height
Shared Rail End Clamp Attachment
Shared Rail Mid Clamp Attachment
End Clamps are used at the ends of a row of PV
panels.
Insert the T-Bolt in the Rail slot and turn
clockwise 90° to engage the head into the slot.
Insert Grounding T-Bolt Holder to lock T-Bolt in
place.
Thread the 1/4” Collar Bolt onto the top of the T-
Bolt as shown. After positioning the End Clamp
firmly against the PV panel frame, using a 7/16”
socket, tighten to 7.5 ft. lbs.
Insert the T-Bolt in the Rail slot and turn
clockwise 90° to engage the head into the slot.
Insert Grounding T-Bolt Holder to lock T-Bolt in
place.
Thread the 1/4” Collar Bolt onto the top of the T-
Bolt as shown. After positioning the Mid Clamp
firmly against the PV panel frame, using a 7/16”
socket, tighten to 7.5 ft. lbs.
Minimum leading edge height to meet a
UL1703 PV module fire standard is 3 inches.
Adjacent solar
panel has been
removed for
clarity