Installation Guide

Wiring
975-0289-01-01 3–17
DC Wiring with Ground Fault Protection
(Renewable Energy Solar Array; Maximum 1000 W)
.
Important:
Renewable energy input may require additional hardware to be
code-compliant. There may also be additional grounding requirements. Be sure
to consult your local electric authority for additional requirements.
Figure 3-15
Connecting the DC Input (Renewable Energy Solar Array)
Example only. Actual installation may vary.
Example only. Consult the PV
Manufacturer for specific wiring
requirements of Solar Arrays.
Torque Neutral and Line terminals
to 1.3 nm (11.5 in-lbs)
Torque Ground terminal
to 1.8 nm (16.0 in-lbs)
Torque Positive, Negative,
and Ground terminals to
20.3 nm (180 in-lbs)