Accessories PNEG-914 Manual
5. Installation
PNEG-914 Flex-Flo 33
8. When a multi-story building is supplied by one auger solely, obtain total drop-out at each outlet.
A time clock MUST be utilized to ensure that all of the feeders are filled at the same time. In the last
hopper on every level, install a hopper level control.
9. With the straight-through tandem system, open only one tank slide at a time when feeding. Operating
the system with both unloader slides open is not recommended since horsepower consumption
increases considerably.
Wire Size by Type
Copper conductors, 1 phase 230V, 3% voltage drop.
In case of conductors supplying several motors on one circuit, the wire size is determined by taking 125%
of the full load current of the largest motor and 100% for all others.
Wire Size by Length of Run
NEC Sec. 225-6/: Conductors in overhead spans must be at least #10 for spans up to 50' and #8
for longer.
Motor
HP
Full Load
Amps
Minimum Allowable Wire Size
In Cable, Conduit or Earth Overhead in Air
Type: R, T, W
Type: RH,
RHW, THW
Bare and Covered
Conductors
1/2 4.9 12 12 10
3/4 6.9 12 12 10
1 8.0 12 12 10
1-1/2 10.0 12 12 10
Length of Run - Ft. (m)
Motor 50 75 100 150 200 250 300 350 400 500 600 700 800 900 1000
Size (15) (22.5) (30) (45) (60) (75) (90) (105) (120) (150) (180) (210) (240) (270) (300)
1/2 HP 12 12 12 12 12 12 12 12 12 10 10 8 8 8 8
3/4 HP121212121212121010888666
1 HP 12 12 12 12 12 10 10 8 8 8 6 6 6 6 6
1-1/2 HP12121210108886666444