Supply Screen
This screen allows the user to specify the operating
parameters for off-board, integrated tanks and indicate
which positions have level sensors installed. See the
Tank Feed Systems manual for information about install-
ing level sensors, see Related Manuals on page 3. The
user may select from the following refill settings: Dis-
abled, Monitor, Manual, Auto Top-Off, Auto Full-Volume.
NOTE: Use the “Disabled” setting if off-board tanks are
not installed.
The following describes system operation when each
tank mode is selected.
• Disabled
• Disables tank operation
• Monitor (2 Sensors)
• The top sensor generates a high level deviation
and the bottom sensor generates a low level
alarm
• Refill is not supported, no button is provided on
the run screens to initiate refill
• Errors will clear when the corresponding condi-
tion clears
• Manual (2 Sensors)
• The top sensor generates a high level deviation
and the bottom sensor generates a low level
alarm
• A button is provided to the user on the run
screens to initiate a manual refill operation at
any time
• Manual refill will run until either the high level
sensor sees material, the user aborts the refill
via the refill button on the run screens, or the
refill time-out expires
• The low level alarm will clear when the condition
clears
• Auto Top-Off (2 or 3 Sensors)
• Automatically selected with three level sensors
selected
• The low level sensor will generate a low level
alarm
• Two level sensors installed: When the high level
sensor does not see material, automatic refill
will begin and continue until either the high level
sensor sees material or until the refill time-out
expires
• Three level sensors installed: When the middle
level sensor does not see material, automatic
refill will begin and continue until either the mid-
dle level sensor sees material or until the refill
time-out expires
• The low level alarm will clear when the condition
clears
• A button is provided to the user on the run
screens to initiate an automatic refill operation
at any time, this button can also be used to
abort a refill operation
• Auto Full-Volume (2 Sensors)
• The low level sensor will initiate an automatic
refill when it does not see material
• Automatic refill will continue until either the high
level sensor sees material or until the refill
time-out expires
• The low level alarm will clear when the condition
clears
• A button is provided to the user on the run
screens to initiate an automatic refill operation
at any time, this button can also be used to
abort a refill operation
Refill Setting
If a refill setting other than Disabled is selected, the user
must set at least two level sensor locations as installed
by checking the check box on the screen. If all three
locations are set to installed, the system will default to
the Auto-Top Off refill setting and operate as follows:
• The low level sensor will generate a low level alarm.
• The high level sensor will generate a high level devi-
ation and abort any automatic refill operation.
• When the middle sensor is not satisfied, automatic
refill will begin and will run until either the middle
sensor is satisfied, the high level sensor generates a
deviation (if the middle sensor fails), or the refill
time-out expires.
• The low level alarm and the high level deviation will
clear when the condition clears.
• A button is provided to the user on the Run screens
to initiate an automatic refill operation at any time.
This button can also be used to abort a refill opera-
tion.