User's Manual
Deviations and A
dvisories
Deviations and Advisories
Therearetwot
ypes of errors that can occur. Errors
are indicated
on the display.
Deviations, indicated by
, require attention, but
not immediately.
Advisories, indicated by
, do not require
attention.
If a deviation or advisory occurs, the system
continues running. The error code and the
or the flash on the screen. If multiple alarms
occur, F2 and F3 have higher priority than MF. They
will appear first and must be cleared first.
Alarm Log Logi
c: If Alarm Auto Clear is enabled,
the system wil
l not log the same alarm twice. For
example, if th
e system goes back forth between low
flow (F2) and n
ormal, the system will log this error
only once, to
keep the log from filling up before the
operator cor
rects the condition.
If Alarm Auto Clear is not enabled, each alarm will
log only once if the operator corrects the condition
and then clears the alarm. The alarm will log twice
if the operator clears the alarm before correcting the
condition.
The following table explains the error type that is
associated with each error code and icon.
Deviations and Advisories
Icon
and
Code
Description
How to Correct and Clear
MF
Advisory alarm. If enabled, the
maintenance totalizer alarm displays
when the user-set maintenance target
value is reached.
Reset Maintenance Totalizer to zero (see
SetupScreen1,page26). Perform maintenance.
Press
to clear alarm. Alarm will not clear until
Maintenance Totalizer has been reset to zero.
F2
Deviation alarm. If enabled, the flow
rate low alarm displays when the
flow rate is lower than the user set
minimum.
Adjust flow rate, reset minimum flow target (see
SetupScreen3,page27), or disable alarm (see
Setup Screen 4, page 28).
Press
to clear screen. The alarm will not clear if the
flow rate is still lower than the user set target.
F3
Deviation alarm. If enabled, the flow
rate high alarm displays when the
flow rate is higher than the user set
maximum.
Adjust flow rate, reset maximum flow target (see
SetupScreen3,page27), or disable alarm (see
Setup Screen 4, page 28).
Press
to clear alarm. The alarm will not clear if the
flow rate is still higher than the user set target.
3A2614F 31