User's Manual
Operation
5. Dispense about 300–500 cc of material into a
graduated cylinder. The amount the system
measures will display in the measured volume
field
.
6. Press
to end th
e calibration.
7. Press
to get to the dispensed volume field
,thenpress to enter the field. Enter
the amount of material in the cylinder.
8. After the volume is entered, the system calculates
the new k-factor
and shows it on Setup
Screen 5.
NOTE: To clear the counter and begin the
calibration again, press
,movebrieflyto
another screen, then return to Setup Screen 4
and start over. If you press
without leaving
the screen, the counter will continue from where
it is, without clearing.
9. Press
to exit the screen.
10. Press
to exit Setup Mode.
Set the Modbus Addresses
See S
etup Screen 7. By default, the Modbus is
set t
oOff
. If you need the Modbus, set the
Modb
us mode to SLAVE
. The address
val
ue is between 1 and 247. The modbus address
cor
responds to the address of the ProControl 1KE.
See
Appendix A for further information.
Set the Flow Ra
te Percent
1. System Setup: See SetupScreen2,page27to
set the upper and lower limit within which the
operator can adjust the flow rate. The settable
range is 0 to 99.9 percent, but the I/P pressure
transducer requires a minimum of 22 to 25 flow
rate percent target to start flow. Therefore, the
operational range is about 22 to 99.9 percent.
See Table 1.
Table 3
Flow Rate
Target
I/P Current Effect
0–about 20
percent
0–4.0 mA
No flow
22%-25%
4.4–5.0 mA
Lowest flow
rate
55% — 60%
11–12 mA
Middle fl
ow
rate
99.9%
20 mA
Highest flow
rate
2. Operator: See Run Screen 1, page 24 to adjust
the flow rate within the set limits.
Update the Software
Software updates are installed using a software token
(PN 16P892), which is sent automatically when a new
version of the software is released. Manual 3A1244
will accompany any necessary software updates.
Follow all instructions and warnings in Manual
3A1244 to update your ProControl 1KE software.