User's Manual

Appendix A - Modb
us Variable Map
Read/Write 402017
Calibration, Measured
Volume
32 Bit pulses 0 32-bit
Read/Write 402019
Calibration,
Actual
Dispensed Vo
lume
32 Bit
cc
032-bit
Table 3 Setup Registers
Register
Permissions
Informer
Modbus
Register
Description
Size
Units Low
Limit
High
Limit
Notes
Read/Write 403000
Communication, Modbus Mode
16 Bit
0=off, 1=on
01
Read/Write 403001
Communication, Modbus Address
32 Bit 1-247 1 247
Read/Write 403003
Communication, Modbus Baud
Rate
16 Bit 0=9600,
1=19200,
2=38400,
3=578600,
4=115200
04
Read/Write 403004
Communication, Modbus Parity
16 Bit 0=None,
1=Odd,
2=Even
02
Read/Write 403005
Communication, Modbus StopBits
16 Bit
none
12
Read/Write 403006 Display, Date Format 16 Bit 0=mm/dd/yy,
1=dd/mm/yy,
2=yy/mm/dd
02
Read/Write 403007 Display, Backlight Timer 16 Bit min 0 99
Read/Write 403008 Display, Maintenance Totalizer
Alarm Enable
16 Bit
0=off, 1=on
01
Read/Write 403009 Display, Flow Rate Alarm Enable 16 Bit
0=off, 1=on
01
Read/Write 403010
Display, Alarm Auto Clear
16 Bit
0=off, 1=on
01
Read/Write 403012 Units, Flow Rate 16 Bit 0=cc/min,
1=l/min,
2=gal/min
02
Read/Write 403013 Units, Batch Volume 16 Bit 0=cc, 1=l,
2=gal
02
Read/Write 403014
Units, Grand Volume
16 Bit 0=cc, 1=l,
2=gal
02
Read/Write 403015
System, Maintenance Target
32 Bit
cc
0 999999
Read/Write 403017
System, Flow Rate Maximum
32 Bit
cc
0 999000
Read/Write 403019
System, Flow Rate Mininimum
32 Bit
cc
0 999000
Read/Write 403021
System, Meter K-Factor
16 Bit
cc
10 5000
( / 1000)
36 3A2040E