Alarm Troubleshooting
96 3A1080C
E-9: MIX_IN_SETUP_ALARM
Cause Solution
Attempt to operate system while in Setup mode. System must be in Standby to change current recipe,
and cannot be operated.
E-10: REMOTE_STOP_ALARM
Cause Solution
Automation has requested that the system abort all oper-
ations.
Abort operations. Troubleshoot automation system.
E-11: PURGE_VOLUME_ALARM
Cause Solution
ProControl 1KS solvent flow switch is not activated while
purging.
Verify that the gun is not shut off and that the solvent flow
switch is activated while purge is taking place.
Minimum flush volume is set too high. Increase solvent supply or decrease minimum volume
setting.
No meter pulses during Color/Catalyst Dump. Color change solvent supply not set up or functional.
Check Color Change setup.
E-12: CAN_COMM_ERROR_ALARM
Cause Solution
Communication between the Color Change Module and
the Fluid Station Control Box is interrupted.
Verify that the cable is correctly connected.
Communication between the Color Change Module and
the Fluid Station Control Box is interrupted. The fluid
control board fuse is blown.
Verify condition of fuse and replace if necessary. See
Repair-Parts manual.
E-13: HIGH_FLOW_ALARM or E-14: LOW_FLOW_ALARM (may also be set as Warnings)
Cause Solution
Fluid system is producing too much or too little flow. Troubleshoot fluid system for restrictions, leaks,
exhausted fluid supply, incorrect settings, etc. Increase
or decrease flow rate, as required.
Table 14. Alarm Troubleshooting