Critical Item Checklist
❑
Wire according to F
IG
. 4 on page 8 and F
IG
. 5 on
page 9.
❑
Use Belden 8777 cable or equivalent. It is impor-
tant to use multiconductor cable with 3 individu-
ally shielded pairs.
❑
Ferrite (15D906) must be installed on pressure
transducer wires.
❑
Do not place signal wires in the same conduit as
AC Power wires. For example, the TDC/Position
sensor wires should not share a conduit with the
VFD wires.
❑
Use the following VFD configuration settings:
• analog input scaling
• 4 mA = 0 (zero) Hz
• 20mA = 80 Hz
• Acceleration rate = 1.0 second (for full
range 0-80 Hz)
• Deceleration rate = 0.5 second (for full
range)-80 Hz)