Troubleshooting
Run Run
Run
Up Up
Up
Problem Problem
Problem
Cause Cause
Cause
Solution Solution
Solution
RunUpControllerreads0
psi
Integratedsystems:InvisiPac
systemisINACTIVE
Stand-Alonesystems:PCsystemis
INACTIVE
Integratedsystems:TurnsystemON,run
upwillbeactiveoncesystemisACTIVE
(pumpwillturnon)
Stand-Alonesystems:TurnsystemON,run
upcontrollerwill
Nopressuretoinletofrunup
controller
Ensurepressureisbeingsuppliedtothe
inletofrunupcontroller(checkforvalves
andshutoffsupstreamofcontroller)
RunUpController
producesundesired
results
Improperusersettingsentered
Performcalibrationroutinefoundin
Calibration – Run Up Control
(see
Calibration,page34).
Outputpressuredesiredisgreater
thaninletpressure
Ensureenoughpressureisbeingsupplied
totheinletoftherunupcontroller(standard
calibrationroutinecallsfor100psi)
PLC PLC
PLC
Inputs Inputs
Inputs
and and
and
Outputs Outputs
Outputs
Problem Problem
Problem
Cause Cause
Cause
Solution Solution
Solution
ImproperinputsignalfromPLCSeePLCInputsandOutputsInstallation
(optional),page11forpropersensor
selection/installation
InputfromPLCnotread
byPatternController
Brokenwire
CheckwiringbetweenPatternController
andPLC
ImproperinterfacetoPLCSeePLCInputsandOutputsInstallation
(optional),page11forspecicationsand
properinstallation
OutputfromPattern
ControllernotreadbyPLC
Brokenwire
CheckwiringbetweenPatternController
andPLC