User's Manual

Installation
Grounding
This equipment must be grounded to reduce the
risk of static sparking and electric shock. Electric
or static sparking can cause fumes to ignite or
explode. Improper grounding can cause electric
shock. Grounding provides an escape wire for the
electric current.
1. Verify that the PD2K base unit is properly
grounded. See the PD2K installation manual for
complete grounding instructions.
2. Ground the expansion kit pump(s) as follows:
a. If the added pump is mounted to the PD2K
main unit, verify that the added pump is
grounded by taking a resistance reading from
the ground screw (7) on the added pump
kit’s back panel (2) to the system’s true earth
ground. Resistance must be less than 1 ohm.
b. If the added pump is NOT mounted to the
PD2K main unit, connect a ground wire to
the ground screw (7) on the added pump kit’s
back panel (2). Connect the other end of the
ground wire to the same true earth ground
that the main PD2K unit is connected to.
Verify that the added pump is grounded by
taking a resistance reading from the ground
screw (7) on the added pump kit’s back
panel (2) to the system’s true earth ground.
Resistance must be less than 1 ohm.
Figure
9 Grounding the Pump Expansion Kit
332456B 15