User's Manual

Installation
6 313599P
Installation
Overview
The Endress+Hauser Promass
®
and Cubemass
®
flow
meters provide a configurable and highly accurate
means of measuring fluid flow. The meters use the Cori-
olis principle to measure mass flow and fluid density and
also measure fluid temperature, using an integrated
temperature sensor.
This manual provides information for using the
Endress+Hauser flow meters with the Graco ProMix
2KS/2KE/3KS proportioners, Informer Kits, and ProCon-
trol 1KS/1KE Kits in non-IS systems. See the manual
provided by Endress+Hauser for further meter instruc-
tions.
Hazardous Location Intrinsically
Safe Installation Requirements
See FIG. 6 on page 10.
NOTE: For ProMix 2KE systems, the Coriolis meter can
only be used on non-IS systems 24F080 through
24F083. When installed on these systems, the meter’s
hazardous location intrinsically safe status is voided.
1. Install Coriolis flow meters as explosion proof (USA,
Canada)/flameproof Ex d (ATEX) with passive
intrinsically safe connections for the signal output
circuit only. Installation must be per the manufac-
turer’s installation instructions and applicable codes.
2. Terminals 24 and 25 of optional Endress+Hauser
Coriolis flow meters are installed using intrinsically
safe wiring methods. Observe manufacturer’s
instructions for installation and use.
For the United States and Canada, install all
other wiring for Coriolis flow meters using explo-
sion proof wiring methods for Division I.
For ATEX installations, install all other wiring for
Coriolis flow meters using Flameproof, Ex d,
wiring methods for Zone 1.
Fluid Supply
Avoid having solids enter the flow meter. Thor-
oughly flush fluid supply lines before installing the
meter.
Do not allow sealing tape to overlap inside pipe con-
nections.
Use an adequately-sized fluid line with a minimal
number of restrictions (valves or bends) to avoid tur-
bulence and cavitation.
To avoid electric shock, turn off equipment power
and shut off power at main circuit breaker before
installing.
All electrical wiring must be done by a qualified
electrician and comply with all local codes and regu-
lations.
Do not substitute system components as this may
impair intrinsic safety.
Protect the meter from friction and impact.
NOTICE
To avoid damaging electrical components, keep liq-
uids away from the meter sensor.