Meter Signal Cable
1. See FIG. 6 on page 10. Route the 20 ft (6.1 m) sig-
nal cable (4) into the fluid panel and through a strain
relief (SR) on the left side of the fluid panel enclo-
sure or control box.
2. See F
IG. 7 for ProMix 2KS/3KS and ProControl
1KS, and F
IG. 8 on page 12 for ProMix 2KE.
a. ProMix 2KS/3KS and ProControl 1KS: Connect
the signal cable’s green ground wire to the
ground terminal bar (GT). Connect the white
and black wires to J3 on the fluid panel control
board (CB). Use pins 2-3 for Flow Meter A and
pins 5-6 for Flow Meter B. See T
ABLE 1 on
page 13 for signal cable connections for addi-
tional meters.
b. ProMix 2KE: See F
IG. 8 on page 12. Connect
the signal cable’s green ground wire to the
ground terminal bar (GT). For Flow Meter A,
connect the black wire to pin 13 and the white
wire to pin 14 on the left terminal strip, as
shown. Connect Flow Meter B to the right termi-
nal strip, pins 13 and 14. Coriolis meters do not
have a red wire and do not use pin 12.
For ATEX installations, the signal cable (4) shall exit
the Coriolis meter through a cable gland or conduit
sealing device ATEX certified for at least Ex d IIA. For
US and Canadian installations, the signal cable (4)
shall exit the Coriolis meter through a seal fitting
listed/approved for at least Class 1, Division 1, Group
D. See F
IG. 6 on page 10.
FIG. 7. Signal Cable Connections (ProMix 2KS/3KS and ProControl 1KS)
1
2
3
4
5
6
J3
COM (BLACK)
SIG (WHITE)
SHIELD/GRN
COM (BLACK)
SIG (WHITE)
SHIELD/GRN
FLOW METER A
FLOW METER B
GROUND
TERMINAL
Coriolis Flow Meter Signal Wire Schematic
J3 Connector;
see wiring
schematic above