Instructions-Parts Coriolis Meter Kits 313599P EN For use with Graco ProMix® 2KS/2KE/3KS Proportioners, Informer® Fluid Monitoring Kits, and ProControl™ 1KS/1KE Management Kits for Fluid and Air, in non-IS systems. Uses vibration to measure fluid flow in low flow applications or with light viscosity, shear sensitive, or acid catalyzed materials. For professional use only.
Models Contents Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Hazardous Location Intrinsically Safe Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . .
Related Manuals Related Manuals See the following manuals for additional information on the ProMix 2KS/2KE/3KS, Informer, and ProControl 1KS/1KE.
Warnings Warnings The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When these symbols appear in the body of this manual, refer back to these Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.
Warnings WARNING SKIN INJECTION HAZARD High-pressure fluid from gun, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment. • Do not point gun at anyone or at any part of the body. • Do not put your hand over the spray tip. • Do not stop or deflect leaks with your hand, body, glove, or rag. • Do not spray without tip guard and trigger guard installed.
Installation Installation • • • • To avoid electric shock, turn off equipment power and shut off power at main circuit breaker before installing. All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations. Do not substitute system components as this may impair intrinsic safety. Protect the meter from friction and impact. 2. Terminals 24 and 25 of optional Endress+Hauser Coriolis flow meters are installed using intrinsically safe wiring methods.
Installation Location Vertical Mounting ProMix 2KS/2KE/3KS and ProControl 1KS NOTE: Do not mount the meter so the fluid line runs horizontally across the vertical mounting surface. • The meter measures the flow at the location it is installed, so install the flow meter as close as possible to the proportioner component A or B dispense valve. • The meter must be located within 20 ft. (6.1 m) of the proportioner fluid panel. The Graco-provided meter signal cable assembly (4) must be used.
Installation Fluid Line Connection Fluid Flow Downward Flow If this method is used, install the check valve at the meter outlet. This provides back pressure in the meter, ensuring that the fluid flow remains smooth and even. See FIG. 2. Check hoses, tubes, and couplings daily. Tighten connections before operating. Replace worn or damaged parts immediately. Connect the fluid supply line to the meter inlet. Connect the 5 ft (1.
Installation ProMix 2KS/2KE/3KS and ProControl 1KS Cable Connections Meter Power Cable (ProMix 2KS/3KS 4. There are two knockouts on the top of the EasyKey enclosure. Knock out one, depending on whether the Coriolis meter will be on the A or B side. 5. Apply the A and B labels (11) as shown in FIG. 4. Install the strain relief (12) as shown in FIG. 5. and ProControl 1KS only) See Hazardous Location Intrinsically Safe Installation Requirements on page 6 and FIG. 6 on page 10.
Installation NON-HAZARDOUS AREA HAZARDOUS AREA 1/4 npt(m) fluid inlet CB 1 GT Coriolis Meter SR 3 EasyKey; see FIG. 5 Fluid Panel; see FIG.
Installation Meter Signal Cable For ATEX installations, the signal cable (4) shall exit the Coriolis meter through a cable gland or conduit sealing device ATEX certified for at least Ex d IIA. For US and Canadian installations, the signal cable (4) shall exit the Coriolis meter through a seal fitting listed/approved for at least Class 1, Division 1, Group D. See FIG. 6 on page 10. 1. See FIG. 6 on page 10. Route the 20 ft (6.
Installation Flow Meter B Connections; see wiring schematic below Flow Meter A Connections; see wiring schematic below $/$50 0$1,)2/' %/$&. 5(' %/$&. 5(' %/$&. 5(' %/$&. 5(' %/$&. 5(' %/$&. 5(' %/$&. 5(' 385*( $ 9'& :$< 62/(12,' '26( $ 385*( % '26( % '26( $ 9'& :$< 62/(12,' '26( $ *)% ; &$%/( 3:5 5(' &20 %/$&.
Installation Power and Signal Cable Connections at Meter -27 +26 4 -25 +24 -23 +22 The signal cable (4) is factory assembled to the meter. The power cable (PC) is user-provided. If cables need servicing or replacement, see FIG. 9 and Table 1 to connect to meter.
Installation Informer and ProControl 1KE Cable Connections. METER 21 Meter Power Cable 22 -27 +26 -25 +24 -23 +22 -21 +20 N (L-) 2 L1(L+) 1 TERMINAL 1 To avoid electric shock, disconnect power source before doing electrical wiring. All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations. POWER 20 The meter is powered by a user-suppled 24V, 1 A, 24W. power supply. Order Graco power supply 120369, if desired.
Operation Operation Start Up When all electrical and fluid connections are complete, reconnect the power source and turn it on. Check I/O Board Jumper (only if necessary) NOTICE If the meter does not operate after following all procedures in the Installation section, starting on page 6, check the position of the I/O circuit board jumper as follows. To avoid damaging the circuit board, wear a grounding strap on your wrist and ground appropriately.
Operation Using Promass Meter with ProMix 2KS/2KE/3KS or ProControl 1KS System Basic Installation Settings 5. To select a Function, press + or – . The function matrix consists of groups which have a set of related functions. See Promass Meter Function Matrix on page 18. NOTE: To enable meter programming, you need to enter the access code. The factory setting is 80. See the Endress+Hauser manual to change the access code. To access groups and functions: 6.
Operation Promass Meter Measuring Values The following are the recommended settings for using the Promass meter with the proportioner. If a value is not mentioned, use the default Endress+Hauser setting.
OPERATION MODE SIMULATION FREQ. PULSE/FREQ. OUT SIM. FAILSAFE MODE SERIAL NUMBER SW-REV. AMP. SENSOR VERSION AMP. HW VERSION ACTUAL SYS. COND. SIMULAT. SYSTEM SUPERVISION TEMP. COEF. KM TEMP. COEF. KM 2 FLOW DAMPING TEMP. COEF. KT EPD RESPONSE TIME DEVICE ID ZERO POINT ADJUST FAILSAFE MODE SIMULATION CURR. TEST DISPLAY UNIT PRESSURE 313599P I/O MODUL TYPE SENSOR TYPE SIM MEAS. PREV. MEASURING SYS. COND. VALUES SW-REV. I/O SW-REV. S-DAT VALUE SIM. MEAS. ASSIGN SYS.
Operation Using Cubemass Meter with ProMix 2KS/2KE/3KS, Informer, or ProControl 1KS/1KE System Basic Installation Settings The function matrix consists of groups which have a set of related functions. See Cubemass Meter Function Matrix on page 20. To access groups and functions: 1. NOTE: To enable meter programming, you need to enter the access code. The factory setting is 84. See the Endress+Hauser manual to change the access code. 5. Select a function.
Operation Cubemass Meter Function Matrix Quick Setup QS Commission Language HOME POSITION Pre-setting Selection pre-settings Delivery Settings Actual Settings Selection system units Mass Flow Volume Flow Corr. Vol. Flow Density Temperature Unit Mass Flow Unit Volume Flow Unit Corr. Vol. Flow Unit Density Unit Temperature Unit Totalizer Unit Totalizer Corr. Vol. Calculation Reference Calculated Unit Ref. Density Exp. Coeff. Lin Fix. Density Exp. Coeff. Quit Ref.
Operation Cubemass Meter Minimum Required Setup Table The following are the recommended settings for using the Cubemass meter with the proportioner. If a value is not mentioned, use the default Endress+Hauser setting.
Parts Parts ProMix 2KS/2KE/3KS and ProControl 1KS Kits 15V806 Coriolis Meter Kit Promass 80A Meter with 1/8 in. (3 mm) metering tube. Includes items 1-12, 19, 20. 258151 Coriolis Meter Kit Promass 80I Meter with 3/8 in. (10 mm) metering tube. Includes items 1-20.
Parts 15V806 Coriolis Meter Kit Promass 80A Meter with 1/8 in. (3 mm) metering tube. Includes items 1-12, 19, 20. 258151 Coriolis Meter Kit Promass 80I Meter with 3/8 in. (10 mm) metering tube. Includes items 1-21. Ref. No. 1 2 4 5 6 10 11 12 16 17 18 19 20 21 Part No. Description 15T633 CORIOLIS FLOW METER, intrinsically safe; 1/8 in. (3 mm) metering tube; used on 15V806 15T634 CORIOLIS FLOW METER, intrinsically safe; 3/8 in.
Parts 24M260 Coriolis Meter Kit Cubemass DCI Meter with 1/8 in. (3 mm) metering tube. Includes items 1-19. 24M261 Coriolis Meter Kit Cubemass DCI Meter with 1/4 in. (6 mm) metering tube. Includes items 1-19. Detail of Top of EasyKey 18 19 4 1/4 npt inlet TI13724a 1 11 Detail of Inside of EasyKey (B Side Connection Shown) 16 12 8 6 7 10 1/4 npsm outlet 2 Ref. No. 1 2 4 6 7 24 TI13723a TI18855a Part No. Description 16M510 CORIOLIS FLOW METER, intrinsically safe; 1/8 in.
Parts Informer and ProControl 1KE Kits 24N525 Coriolis Meter Kit Cubemass DCI Meter with 1/4 in. (6 mm) metering tube. Includes items 1-19. 18 19 9 1/4 npt inlet 21 1 22 16 20 8 6 7 10 1/4 npsm outlet 2 TI18855a Ref. No. Part No. Description Qty. 1 16M519 CORIOLIS FLOW METER, intrinsi1 cally safe; 1/4 in.
Promass Dimensions Promass Dimensions N R M P S B A F L E K G J C D H TI4936a Dimensions - inches (mm) 26 A B C D E F G H 12.4 (315) 11.14 (283) 1.26 (32) 17.13 (435) 8.66 (220) 11/16 6.89 (175) 19.57 (497) J K L M N P R S 7.68 (195) 5.91 (150) .14 (3.5) 8.19 (207) 8.94 (227) 6.61 (168) 7.36 (187) 6.
Cubemass Dimensions Cubemass Dimensions G H C 1/4 nps fluid inlet B A 1/4 nps fluid outlet D TI8857a F TI8856a E Dimensions - inches (mm) A B C D E F G H 12.52 (318) 10.65 (271) 9.47 (241) 6.89 (175) 9.66 (245) 7.89 (200) 8.92 (227) 7.
Mounting Hole Dimensions Mounting Hole Dimensions 15V806 Coriolis Meter Kit 258151 Coriolis Meter Kit Four 0.26 in. (6.6 mm) mounting holes Four 0.25 in. (6.3 mm) mounting slots TI16270a TI13718b 7.11 in. (181 mm) TI16272a 24M260, 24M261, and 24N525 Coriolis Meter Kits 6.89 in. (175 mm) 3.54 in. (90 mm) Four 0.38 in. (9.5 mm) mounting holes 3.44 in. (87 mm) 8.66 in.
Technical Data Technical Data Part No. 15V806 and 258151 Coriolis Meter Kits Maximum Fluid Working Pressure Fluid wetted parts (meter) U.S. Metric 2300 psi 16 MPa, 160 bar 1.4539/904L stainless steel alloy C-22 2.4602/N 06022 Fluid wetted parts (hose and fittings) Fluid Temperature Range* Maximum Ambient Temperature* 303, 304 stainless steel, PTFE 41-122° F 5-50° C 122° F 50° C Fluid Inlet/Outlet 4-VCO-4 Face Seal Power and Signal Cable Entry 1/2 npt strain relief Resolution settable 0.
Graco Standard Warranty Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective.