Product Manual
3922108-01D PRO35-115 / PRO35-115RD
Install Nozzle Hanger
(Not applicable to pumps with -RD sufx)
Attention: The nozzle hanger for your pump was removed
before shipping to protect against damage.
To reinstall the nozzle hanger follow the steps below.
1. Remove the two ¼"-20 x ½" bolts and the two at
washers from the switch coverplate.
2. Place the two bolts through the nozzle cover and then
place the two at washers on the bolts. The washers
are used as spacers to set the nozzle hanger away
from the switch coverplate.
3. Align the bolts with the two threaded holes on the
switch coverplate; thread the bolts into the holes.
Torque bolts to 45-60 in/lb (Figure 1).
FIGURE 1
Switch Locking Lever
Attention: The PRO35-115RD remote dispenser pump
incorporates an external switch locking lever that locks the
pump switch in the “ON” position. The pump is typically
shut off using the remote dispensing device “ON-OFF”
mechanism.
Electrical Connections
Pump must be installed by a licensed electrician and conform
to National Fire Protection Association (NFPA) codes 30 and 70.
You, as the owner, are responsible for seeing that the installation
and operation of your pump complies with NFPA codes as well
as any applicable state and local codes. Rigid conduit must be
used to install wiring.
Failure to follow these wiring instructions may result in death or
serious injury from shock, re or explosion.
The pump must be properly grounded to avoid personal injury.
Operating an ungrounded or improperly grounded pump may result
in death due to electrical shock, re or explosion.
DANGER
Electrical wiring and connections must be made only by
a licensed electrician in accordance with national, state
and local electrical codes regarding Class I, Division 1,
Group D locations. Other codes may apply.
Thread for the conduit connection at the pump electrical
box is ½ in. FNPT.
A standard 15-amp breaker is recommended.
This pump is equipped with an auxiliary AC accessory
lead. The third wire (red) is to be used to energize a
control circuit that operates a device such as a signal
light or a solenoid operated valve. Maximum amp draw
on the control circuit is 1 amp. If you do not need this
feature, ensure that the wire is insulated and enclosed
within the electrical cavity of the pump.
Connect pump to the proper voltage source. PRO35 series pumps
are designed to operate on 115 VAC, 60 HZ or 230 VAC, 60 HZ.
Connection to improper voltage will damage pump. Pump is set
at factory for low voltage (115-volt). For high voltage applications
(230-volt) see wiring diagram located inside electrical coverplate.
CAUTION
Wiring Details
1. Remove electrical coverplate (Figure 2). Install con-
duit and cable from switchbox to pump electrical box.
Wiring must be in accordance with Class I, Division 1
requirements in the applicable national electrical code.
A
DETAIL A
SCALE .75
FIGURE 2
2. Attach ground wire using the green ground screw lo-
cated inside the electrical box (Figure 3). Connect the
power cable to the pump wiring per the wiring diagram
located inside the electrical coverplate. Secure with
wire nuts.
FIGURE 3
3. Position wires inside the electrical box. Replace
electrical coverplate with all seven screws and tighten
securely.