Application
Designed to safely transfer low viscosity petroleum fuels such as gasoline (up to 15% alcohol blends
such as E15), diesel fuel (up to 20% biodiesel blends such as B20) and kerosene. Pump is designed
for permanent mounting on vented storage tanks.
Pump Housing
Cast Iron
Performance:
Pump Rate Up to 25 GPM (94 LPM) Up to 25 GPM (94 LPM)
Duty Cycle 30 min. ON, 30 min. OFF 30 min. ON, 30 min. OFF
Suction Lift: Up to 15 feet (4.6 meters) Up to 15 feet (4.6 meters)
Discharge Lift: Up to 10 feet (3 meters) Up to 10 feet (3 meters)
Operating Temperature
-20° F to +125° F (-29° C to +52° C)
XTS Operating Temperature
Extreme Temperature Series pumps are capable of operation down to -40° F.
Any pump operation below -20° F has not been evaluated by UL.
Bypass Pressure
20 PSI
Electrical Specications:
Input 12-volt DC 24-volt DC
Current Draw 35 amps 20 amps
Motor 2000 RPM, 4/10 hp (300 watts) 2000 RPM, 4/10 hp (300 watts)
Motor Approval cULus Listed. Class I, Division 1, Group D cULus Listed. Class I, Division 1, Group D
Motor Protection 40 amp circuit breaker 20 amp circuit breaker
Cord* 15 feet of 10 gauge (4.6 meters) 15 feet of 10 gauge (4.6 meters)
Fuse 40 amp 20 amp
Mechanical Connection:
Bung 2 inch NPT 2 inch NPT
Inlet 1 inch NPT 1 inch NPT
Outlet 1 inch NPT 1 inch NPT
Accessories:
Hose Type Buna-N Electrically Conductive Discharge Hose Buna-N Electrically Conductive Discharge Hose
Hose Size 1 in. NPT x 1 in. 18 ft. (5.5 m) 1 in. NPT x 1 in. 18 ft. (5.5 m)
Manual Nozzle 1 in. NPT Diesel 1 inch Diesel
Automatic Nozzle 1 in. NPT Diesel 1 inch Diesel
Weight:
PRO25-012PO 56.7 lbs/25.7 kg N/A
PRO25-012MD 69.7 lbs/31.6 kg N/A
PRO25-012AD 71.9 lbs/32.6 kg N/A
PRO25-024PO N/A 56.7 lbs/25.7 kg
PRO25-024AD N/A 71.9 lbs/32.6 kg
SPECIFICATIONS
TROUBLESHOOTING
SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
G. MOTOR OVERHEATS
1. Pumping high viscosity uids Pump only low viscosity uids.
2. Clogged lter assembly Clean lter assembly.
3. Clogged or broken suction pipe Remove pump and clear suction pipe, replace as needed.
4. Duty cycle too long Duty cycle is 30 minutes ON and 30 minutes OFF.
5. Motor failure Ball bearings damaged. UL Listing requires specic treatment for
motor replacement, contact factory.
6. Bypass poppet clogged Remove bypass poppet and clean.