Product Manual A

In order to preserve the UL Listing for pump safety, return
the entire pump to the factory for repair or replacement.
For products serviced outside the factory, the UL name-
plates must be defaced to indicate that the equipment
may no longer meet the requirements for UL Listing.
This does not apply to products serviced outside the
factory under the UL program for Rebuilt Motors for Use
in Hazardous Locations.
For warranty consideration, parts, or other service infor-
mation, please contact your local distributor. If you need
further assistance, contact the GPI Customer Service
Department in Wichita, Kansas, during normal business
hours. A toll free number is provided for your convenience.
1-800-835-0113
To obtain prompt, efcient service, always be prepared
with the following information:
1. The model number of your pump.
2. The manufacturing date code of your pump.
For the M-3130 series, the date code is located on the
motor nameplate.
For warranty work, always be prepared with your original
sales slip or other evidence of purchase date.
Please contact GPI before returning any pump. It may
be possible to diagnose the trouble and nd a solution
with a telephone call. GPI can also inform you of any
special requirements you will need to follow for shipping.
Do not return the pump without authority from the
Customer Service Department. Due to strict govern-
ment regulations, GPI cannot accept pumps unless
they have been drained and cleaned.
7
The M-3130 fuel pump is designed to safely transfer low
viscosity petroleum fuels such as gasoline (up to 15%
alcohol blends such as E15), diesel fuel (up to 20%
biodiesel blends such as B20) and kerosene. The pump
is designed for permanent mounting on vented storage
tanks, either in-ground or above-ground. RAINPROOF
for outdoor use.
Performance
Pump Rate: Up to 30 GPM (114 LPM)
Duty Cycle: 30 minutes ON, 30 minutes OFF
Dry Prime: 15 ft. (4.6 m) maximum
Discharge Lift: 10 ft. (3 m) maximum
Operating Temperature
-20° F to +125° F (-29° C to +52° C)
Operating Pressure
25 PSI
Electrical
Input: Factory set at 115 VAC, 60 Hz. Optional
to set at 230 VAC, 60 Hz.
Conduit: 1/2-inch FNPT
Current Draw: 9.8 amps at full load (at 115 VAC, 60 Hz)
Motor: 3/4 HP, 1725 RPM induction type
provided with an internal auxiliary
temperature-limiting device
Mechanical Connections
Bung: 2-inch MNPT
Inlet: 1-1/4-inch FNPT
Outlet: 1-inch FNPT
Accessories
Hose: 1 in. x 12 ft. (3.7m) Buna-N electrically
conductive
Nozzle: 1 in. manual leaded spout or
1 in. automatic diesel
Security: Nozzle can be padlocked
Ship Weight 69 lbs. (31 kg) - Pump only
77 lbs. (35 kg) - With manual nozzle
79 lbs. (36 kg) - With automatic nozzle
CAUTION