Product Manual

12
1
1
2
2
A A
B B
TITLE
SIZE
DWG NO
REV
SCALE:
SHEET OF
DRAWN
CHECKED
APPD.
ECN
DO NOT SCALE DRAWING
MAT'L
WICHITA, KANSAS 67220 U.S.A.
WT. LBS.
CAGE CODE
STANDARD
DRAFTING REFERENCES
ASME Y14 SERIES
UNLESS OTHERWISE SPECIFIED,
DIMENSIONS ARE IN INCHES
AND TOLERANCES ARE:
DECIMAL
.XX ± .03
.XXX ± .010
ANGLES
MACH ± 0°30'
FORMED ± 2°

1 1
JJW
3/28/2012
A
3550
DR 5-30 PULSE OUTPUT
(INTRINSIC SAFE INSTALLATION)
126340-01
A
Non-Hazardous Location
Hazardous Location
Intrinsically Safe Apparatus
U.L. LISTED
INTRINSIC
SAFE
BARRIER
SAFE AREA
CUSTOMER
EQUIPMENT
ENTITY PARAMETERS:
CLASS I, DIV.1, GROUP D
GPI PN: 126300-11
(DR 5-30-6N)
GPI PN: 126300-12
(DR 5-30-8N)
GPI PN: 126300-13
(DR 5-30-12N)
A
DETAIL- A
(WIRING CONNECTION)
SEE OWNER'S MANUAL 922092-01
FOR DETAILS ON STRAIN RELIEF
AND CABLE INSTALLATION.
Vmax (Ui) = 6.8 VoltsDC
Imax (Ii) = 200 mAmps
Pmax (Pi) = 0.2 Watts
Ci = 15 uF
Li = 0 mH
Vmax (or Ui)
Voc or Vt (or Uo)
Imax (or Ii)
Isc or It (or Io)
Ci + Ccable
Ca (or Co)
Li + Lcable
La (or Lo)
Pmax (or Pi)
Po
NOTES:
1. Barrier Configuration must be UL Listed.
2. Barrier Manufacturers installation drawing must be
followed when installing the system.
3. Installation should be in accordance with ANSI/ISA
RP12.6 "INSTALLATION OF INTRINSICALLY SAFE
SYSTEMS FOR HAZARDOUS LOCATIONS" and the
National Electric Code (ANSI/NFPA 70).
4. Capacitance and inductance of the field wiring from the
intrinsically safe equipment to the associated apparatus
shall be calculated and must be included in the system
calculations as shown in TABLE 1. Cable capacitance,
Ccable, plus intrinsically safe equipment capacitance, Ci,
must be less than the marked capacitance, Ca (or Co),
shown on any associated apparatus used. The same
applies for inductance (Lcable, Li and La or Lo,
respectively). Where the cable capacitance and
inductance per foot are not known, the following values
shall be used: Ccable = 60pF/ft., Lcable = 0.2 µH/ft.
TABLE 1:
I.S. Equipment Associated Apparatus
If Po of the associated apparatus is not known, it may be
calculated using the formula Po=(Voc*Isc)/4 = (Uo*Io)/4.
WARNING! Only use 4 each, Size AA (1.5V)
Energizer® L91 Lithium/Iron Disulfide batteries.
To reduce the risk of explosion, do not mix new
with used batteries.
COM
SIG
CONTROL DRAWING (126340-01)