______________________________________________________________ Operating Instructions METRAFLEX 3000 METRAFLEX 3001 / 3001XL METRAFLEX 3003 / 3003XL (3-Phase Set) Flexible AC Current Probe 3-349-530-37 2/12.
_______________________________________________________________ Order Reference Order No. METRAFLEX 3000 Flexible AC Current Probe 30/300/3000A ............ Z207E 61 cm (24”), battery supply, 3V output on 4mm safety plugs METRAFLEX 3001 Flexible AC Current Probe 30/300/3000A ............ Z207F 61 cm (24”), battery/external supply, 3V output on 4mm safety plugs; incl. supply cable for MAVOWATT|50 METRAFLEX 3001XL Flexible AC Current Probe 30/300/3000A ............
______________________________________________________________ Thank you for buying this product. For safety reasons and optimum use of this instrument read through the operating instructions very carefully. Table of Contents 1. SAFETY ........................................................................................ 20 2. INTRODUCTION ........................................................................... 22 3. SPECIFICATIONS ................................................................
_______________________________________________________________ 1. SAFETY The following symbols appear on the products: Attention! Refer to Manual Double/Reinforced Insulation Do not apply around or remove from HAZARDOUS LIVE conductors without additional protective means. “Additional protective means” can be: - de-energizing the circuit - wearing protective clothing suitable for high voltage work. Do not dispose of this product as unsorted municipal waste. Contact a qualified recycler for disposal.
______________________________________________________________ The flexible current transformer is manufactured and tested in accordance with safety regulations IEC/EN 61010-1 / -031 /-2-032. If used for its intended purpose, safety is assured for the user, the device and the DUT. Read the operating instructions carefully and thoroughly before placing the device into operation. Observe and follow all points included therein. Make the operating instructions accessible to all users.
_______________________________________________________________ 2. INTRODUCTION The METRAFLEX are AC current probes utilising Rogowski principle. They can be used to measure AC current up to 3000A by being connected to an appropriate measuring device (multimeter, data logger, power analyser etc.). The flexible probe allows current measurements on conductors that are hard to reach. The probes provide an AC output voltage of 0…3V (METRAFLEX 3000/3001/3003) or 0…1.
______________________________________________________________ 3. SPECIFICATIONS METRAFLEX 3000 METRAFLEX 3001 METRAFLEX 3003 METRAFLEX 3001XL METRAFLEX 3003XL Measuring ranges 30A 300A 3000A 30A 300A 3000A Scaling factor 10 100 1000 20 200 2000 100mV/A 10mV/A 1mV/A 50mV/A 5mV/A 0,5mV/A ±1% of rdg. ±0,1A ±1% of rdg. ±1A Output sensitivity Accuracy (45-65Hz) 8 mVrms Noise 2 mVrms ±1% of rdg. ±0,1A 8 mVrms 1 pair 4mm safety plugs Output Connector ±1% of rdg.
_______________________________________________________________ Enclosure Material ARNITE T06-200 SNF, UL94 V0 Degree of Protection IP40 Dimensions 110 (l) x 65 (w) x 23 (d) mm Output connection 0.5m coax cable terminated with 4 mm safety plugs Probe Probe length 61 cm (24 inches), double insulated on request: 91 cm (36 inches),122 cm (48 inches) Probe diameter 9.9mm (0.39 inches) Output cable 2m long (78.
______________________________________________________________ METRAFLEX Frequency Response Relative op % ref 50Hz 2,00 0,00 10 100 1000 10000 100000 -2,00 30A range -4,00 300A range -6,00 -8,00 -10,00 Frequency Hz METRAFLEX Phase Response 20 Phase error degrees 15 10 30A range 5 300A range 0 10 100 1000 10000 100000 -5 -10 Frequency Hz _______________________________________________________________ 25
_______________________________________________________________ 4. OPERATION 4.1 BATTERY INSTALLATION AND BATTERY STATUS Never replace batteries with flexible measuring head installed on conductor to be tested or output connected to a measuring device. Never operate the unit without the battery cover fitted. The METRAFLEX require two AA MN1500 LR6 alkaline batteries for operation. The battery compartment is accessed from the rear of the electronics enclosure.
______________________________________________________________ 4.2 EXTERNAL POWER SUPPLY Alternatively, the METRAFLEX can also be supplied by an external DC voltage source (except METRAFLEX 3000). The connection is made at the connector on the side of the electronics housing. Supply voltage range, see Technical Data.
_______________________________________________________________ 4.3 CONNECTING TO MEASURING DEVICE Read safety section of instructions before operating this product. METRAFLEX 3000: Plug the output cable of the current sensor into the voltage measuring input terminals of the multimeter (black to GND, red to V) and switch it to V AC. METRAFLEX 3001/3003: Plug each output cable of the current sensor to the current measuring input terminals “I” on the MAVOWATT|50.
______________________________________________________________ 4.4 CONNECTING TO THE CIRCUIT TO BE MEASURED It is strongly recommended to de-energize the circuits to be measured when making connections to the installation. If it is necessary to make connections on energized circuits they must be made by qualified and authorized personnel only observing the required safety precautions.. Never apply the probe around bare conductors with voltage levels over 1000V (CAT III) or 600V (CAT IV) to ground.
_______________________________________________________________ 4.5 MEASUREMENT To activate unit, move the rotary switch from the “off” position to the required measuring range. If the value of current being measured is unknown, first select the highest range and then reduce accordingly. The red and the orange LED might flash when the unit is switched on or when the measuring range is changed.
______________________________________________________________ 5. MAINTENANCE Do not use METRAFLEX if damaged. Always inspect the integrator unit, connecting cable, and flexible probes for damage before use. To avoid electric shock, keep the METRAFLEX clean and free of surface contamination. Use Isopropyl alcohol to clean the electronics unit and the probe. Make sure the flexible probe, connecting cable, and electronics enclosure are dry before further use. 6.
_______________________________________________________________ 7. PRODUCT SUPPORT If required please contact: GMC-I Messtechnik GmbH Product Support Hotline Phone: +49 911 86 02-0 Fax: +49 911 86 02-7 09 E-mail: support@gossenmetrawatt.com 8.
______________________________________________________________ GMC-I Messtechnik GmbH Südwestpark 15 D-90449 Nürnberg DEUTSCHLAND Tel. +49 (0)911 8602-111 Fax +49 (0)911 8602-777 e-mail: info@gossenmetrawatt.com www.gossenmetrawatt.