Manual

Technical Data
ENGLISH
Data in compliance with CLC/TR 50579 , EN 62059-32-1, EN 50470-1, EN 50470-3
Direct connection Direct connection
Pulse output built-in communication
S0 Modbus / M-Bus
General characteristics
Housing DIN 43880 DIN 4 modules 4 modules
Mounting EN 60715 35 mm DIN rail DIN rail
Depth mm 70 70
Weight g 412 412
Operating features
Connectivity to three-phase network n° wires 4 4
Storage of energy values and configuration internal FLASH memory - yes yes
Display tariffs identifier for active energy n° 2 T1 and T2 T1 and T2
Approval (according to EN 50470-1, EN 50470-3)
Reference Voltage Un Line to Neutral VAC 230 230
Reference Voltage Un Line to Line VAC 400 400
Reference Current (Iref) A 5 5
Minimum Current (Imin) A 0.25 0.25
Maximum Current (Imax) A 80 80
Starting Current (Ist) A 0.015 0.015
Reference Frequency (fn) A 50 50
Number of phases (number of wires) - 3 (4) 3 (4)
Certified Measures kWh kWh, kWh kWh, kWh
Accuracy Active Energies (accor. to EN 50470-3) and Active Powers class B B
Supply Voltage and Power Consumption
Operating Supply Voltage range VAC 92 ... 276 / 160 ... 480 92 ... 276 / 160 ... 480
Maximum Power Dissipation (Voltage circuit) VA (W) <2 (0.6) < (0.6)
Maximum VA burden (Current circuit) @ Imax VA <0.7 <0.7
Voltage Input Waveform - AC AC
Overload capability
Voltage continuous; phase/phase VAC 480 480
1 second: phase/phase VAC 800 800
continuous; phase/N VAC 276 276
1 second: phase/N VAC 300 300
Current continuous A 80 80
Temporary (10 ms) A 2400 2400
Measuring Features
Voltage range phase/phase VAC 160 ... 480 160 ... 480
phase/N VAC 92 ... 276 92 ... 276
Current range (secondary winding) A 0.015 ... 80 0.015 ... 80
Frequency range Hz 45 ... 65 45 ... 65
Measured Quantities - kWh kWh
Display features
Display type LCD - 9 (2 Decimal) 9 (2 Decimal)
Energy digits dimension mm 6 x 3 6 x 3
Active Energy 7 digits + 2 decimal digits min. ... max. kWh 0.01 ... 9999999.99 0.01 ... 9999999.99
Running Tariff 1 digit - T1 or T2 T1 or T2
Display refresh period s 1 1
Safety
Protective class class II II
AC voltage test (EN 50470-3, 7.2) kV 4 4
Degree of pollution - 2 2
Operational voltage VAC 300 300
Impulse voltage test 1.2/50 μs-kV 6 6
• Housing material flame resistance UL 94 class V0 V0
• Safety-sealing between upper and lower housing part - yes yes
Pulse Outputs (S0 signals) acc. to IEC 62053-3
Pulse Output 1 adjustable - kWh (T1) , kWh , kWh kWh (T1) , kWh , kWh
Pulse Output 2 adjustable - kWh (T2) , kWh , kvarh kWh (T2) , kWh , kvarh
Pulse Rate adjustable p/kWh 1 ... N (
*
) -
(
*
) N - dep. on CT-ratio and
Pulse on Time)
Pulse ON-time adjustable ms 30 ... 100 -
Operating Voltage Min - Max VAC (VDC) 3 ... 28 VAC (5 ... 39 VDC) -
Pulse ON maximum current mA 90 -
Pulse OFF leakage current μA 1 -
Isolation class - SELV circuit -
Embedded communication Modbus
Physical interface RS485 - 3 Wire - - D1, D0, Common (GND)
Internal termination resistor - - 120 Ω
Baud rate adjustable - - 1200-2400-4800-9600
19200-38400
Parity adjustable - - Odd, Even, None
Stop Bit adjustable - - 1. 2
Address adjustable - - 1-247
Isolation class - - SELV circuit
Embedded communication M-Bus
Baud rate adjustable - - 300-600-1200-2400
4800-9600
Unit load - - 1
Isolation class - - SELV circuit
Optical metrological LED
Front mounted red LED (meter constant) proportional to active imp/exp Energy p/kWh 1000 1000
IR Connectable Communication Modules
For communication moduls connection (LAN-TCP/IP / M-Bus / Modbus RTU / KNX) - yes yes
Connection terminals
Screwdriver for mains terminals head with Z +/- POZIDRIV PZ2 PZ2
Screwdriver for tariff and comm. terminals slotted head mm 0.8 x 3.5 0.8 x 3.5
Terminal capacity main current paths solid wire min. (max) mm
2
0 (33) 0 (33)
stranded wire with sleeve min. (max) mm
2
0 (33) 0 (33)
Terminal capacity for tariff and comm. solid wire min. (max) mm
2
0 (4) 0 (4)
stranded wire with sleeve min. (max) mm
2
0 (2.5) 0 (2.5)
Environmental conditions (storage)
Temperature range °C -25 ... +70 -25 ... +70
Environmental conditions (operating)
Temperature range °C -25 ... +55 -25 ... +55
Mechanical environment - M1 M1
Electromegnetic environment - E2 E2
Installation Indoor - yes yes
Altitude (max.) meters <2000 <2000
Humidity yearly average, not condensing - <5% <75%
on 30 days per year (not condensing) - <95% <95%
IP rating - IP51(*)/IP40 IP51(*)/IP40
(*) The metering equipment must be installed inside a cabinet with IP rating IP51 or better.
European conformity marking
Double insulation (protection category II)
CE and metrology mark with indication of year (M22) and registration number of the notified body for module D, country-specific calibration validity period
DIN 43880
EN 50470-1
EN 50470-3
EN 60715
EN 62053-31
IEC 62053-23
Transport and store the instrument only within the limits of permissible ambient conditions. Also use suitable packaging in order to ensure adequate protection
against environmental influences and mechanical stress.
The instrument is maintenance-free. Keep outside surfaces clean.
Clean the instrument only with a dry cloth.
Comply with national recalibration regulations and laws. The calibration period in Germany is 8 years.
A broken manufacturer’s seal means equals invalidated calibration. The instrument must not be used for billing purposes.
If your instrument requires repair, please contact our service department; see Support & Contact.
Unauthorized modification of the instrument is prohibited. This also includes opening the meter.
If it can be ascertained that the instrument has been opened by unauthorized personnel, no guarantee claims can be honored by the manufacturer with
regard to personal safety, measuring accuracy, compliance with applicable safety measures or any consequential damages. If the manufacturer’s seal is da-
maged or removed, all guarantee claims are rendered null and void.
The instruments are guaranteed for a period of 2 years after shipment. The manufacturer’s guarantee covers materials and workmanship. Damage resulting
from use for any other than the intended purpose or operating errors, as well as any and all consequential damage, are excluded.
The following comments refer specifically to the legal situation in the Federal Republic of Germany. Owners or end users who are subject
to other national requirements are required to comply with the respectively applicable national requirements and to implement them correctly
on site
The symbol on the left depicting a crossed-out garbage can on wheels refers to the legal obligation of the owner or end user (German elec-
trical and electronic equipment act ElektroG and German battery act BattG) not to dispose of used electrical equipment and batteries with
unsorted municipal waste (“household trash”).
Old devices, electrical or electronic accessories and waste batteries (including rechargeable batteries) used in Germany can be returned
free of charge to Gossen Metrawatt GmbH or the service provider responsible for their disposal. Further information can be found on our
website.
Standards, Regulations and Directives
Transport & Storage
Maintenance
Recalibration
Repairs & Manufacturer’s Guarantee
Disposal & Environmental Protection
Symbols on the Instrument
Support and Contact
Please contact us at
+49 911 8602-0
Monday – Thursday: 08:00 Uhr – 16:00 Uhr
Friday: 08:00 Uhr – 14:00 Uhr
support.industrie@gossenmetrawatt.com
Please contact GMC-I Service GmbH for repairs, replacement parts and calibration:
+49 911 817718-0
service@gossenmetrawatt.com
www.gmci-service.com
CE Declaration
The device fulfills all requirements of applicable EU directives and national regulations.
We confirm this with the CE mark.
The CE declaration is available on our website:
https://www.gmc-instruments.de/en/services/download-center/download-center/
Gossen Metrawatt GmbH
Südwestpark 15 • 90449 Nürnberg • Germany
Telefon +49 911 8602-0 • Telefax +49 911 8602-669
E-Mail info@gossenmetrawatt.com • www.gossenmetrawatt.com
© Gossen Metrawatt GmbH
• Prepared in Germany
• Subject to change, errors excepted
• PDF version available on the Internet
All trademarks, registered trademarks, logos, product names and company names are the
property of their respective owners.
Notes