Datasheet

GMC-I Gossen-Metrawatt GmbH 7
SYSKONP1500
Computer Controlled Laboratory Power Supply
General
Power supply with 230 V~ nominal line voltage
Power consumption
Line voltage
At nominal load, 1500 W
At no load
230 V~ + 10 / – 15%, 47 to 63 Hz
1925 VA; 1865 W
96 VA; 37 W
Power supply with 115 V~ nominal line voltage
Power consumption
Line voltage
At nominal load, 750 W
At no load
115 V~ + 10 / – 15%, 47 to 63 Hz
1125 VA; 1100 W
55 VA; 36 W
Max. power loss At a nominal load of 1500 W
At a nominal load of 750 W
365 W
350 W
Efficiency At a nominal load of 1500 W
At a nominal load of 750 W
80%
68%
Switching frequency, PFC / DC/DC Typical 47 kHz / 230 kHz
Inrush current Max. 50 A
s
Mains fuse (6.3 x 32 mm, UL) 1 x M 15 A / 250 V
MTBF (mean time between failures) at 40 °C > 50,000 hours
1)
At maximum current setting not including processing time for the previous voltage setting command